Replacement devices: CPU > Replacement device 07KT9x-AD
1.4.1.3.4
Technical data 07KT9x-AD
The technical data described in the existing documentation (chapter 2.2.7) are invalid for the
AC31 adapter and are replaced by the following data.
Further information:
General data
Data
Number of digital inputs
Number of digital outputs
Number of digital inputs/outputs
Number of analog inputs
Number of analog outputs
Supply voltages:
-> UP
-> Fuse for UP
-> Power consumption for UP
-> L+
-> Fuse for L+
-> Power consumption for L+
-> Electrical isolation between UP and L+
Number of serial interfaces
Number of serial interfaces (diagnosis)
Number of parallel interfaces
Program memory
Resolution of the integrated real-time clock
Data of the high-speed hardware counter installed:
-> Number of operating modes
-> Counting range
-> Counting frequency
Cycle time for 1 instruction
44
Ä Chapter 1.3 "System data and CS31 bus system data" on page 4
3ADR010122, 8, en_US
Value
16
16
16
8
4
-> X7 / UP (pin 54), X7 / ZP (pin 45)
-> X8 / UP (pin 64), X8 / ZP (pin 55)
-> X9 / UP (pin 74), X9 / ZP (pin 65)
See Fig. 18
16 A
300 W (per 100W on X7, X8 and X9)
X6 / L+ (pin 40), X6 / L+ (pin 41)
X6 / M (pin 42), X6 / M (pin 43)
See Fig. 18
10 A
10 A
Yes
1x COM2 (for diagnosis and programming
with the Automation Builder software)
1x DIAG (for diagnosis with the Automation
Builder software)
1 special interface for connection of an
external coupler
PM590 2MB
1 s
-> 10
-> 0 ... 4,294,967,295 (double word format, 32
bit)
-> Depending on operating mode
Note: At the counting input, an external
resistor of 470 Ω / 1 W must always be con-
nected upstream.
Binary: min. 0.002 µs, word: min. 0.004 µs,
floating point: min. 0.004 µs
2018/09/24