AC31 Adapters
Replacement devices: CPU > Replacement device 07KT9x-AD
Connection of the supply voltage
Fig. 19: Connection of the supply voltage
Table 12: Connector (X6)
Connector / Terminal
X6 / L+
X6 / L+
X6 / M
X6 / M
X6 / functional earth
In addition to connecting the supply voltage (L+/M) to X6, the supply voltage (UP/ZP) must
be connected to all connectors.
ZP must be connected to all connectors (X1, X2, X3, X7, X8, X9).
UP must be connected to all connectors (X7, X8, X9).
L+/M and UP/ZP must always be supplied with voltage.
Connection for CS31 bus
Table 13: Connector (X5)
Connector / Terminal
X5 / shield
X5 / B2
X5 / B1
26
Pin
40
41
42
43
44
Pin
37
38
39
Terminal "Shield" is internally connected to FE. The previous earthing meas-
ures, e.g. with clip at the switchgear cabinet, are still required.
"System data and CS31 bus system data" on page 4
3ADR010122, 8, en_US
Assignment / Signal
Supply voltage +24 V DC
Supply voltage +24 V DC
Earth connection (0 V)
Earth connection (0 V)
The functional earth (FE) is
connected to the Faston ter-
minal inside the device.
Ensure that no earth loops are
created and that FE and
Faston are connected to the
same earthing potential.
Assignment / Signal
Shield (functional earth)
BUS2
BUS1
Ä Chapter 1.3