4
SETTINGS AND PROCEDURE TO OPERATION
Table 4.5 Setting items of the [Switch setting for I/O and intelligent function module] dialog box
Switch 1
Switch 2
Switch 3 (Lower byte)
Switch 4 to 5
(1) Mode setting (Switch 1)
Select the MES interface module operation mode.
0000h
0001h
0002h
(2) Default operation setting/battery error detection setting (Switch 2)
Select the default operation setting/battery error detection setting for the MES
interface module.
b15
Battery error detection setting
Only for QJ71MES96 MES interface module
0: Detects battery errors.
1: Does not detect battery errors.
* When other than 0 is specified in this area,
"Switch setting error" (0180h) occurs at hardware test.
(a) Default operation setting (bit 0, 1)
Switch number
Table 4.6 Mode setting (Switch 1) setting items
Setting
Item
number
Online
Hardware test
Self-loopback test
to
Specify "0". *
Figure 4.9 Default operation setting/battery error detection setting (Switch 2)
Set whether to operate [Account setting] and [Network settings] with their default.
1) [Account setting] (bit 0)
0: Operates according to [Account setting].
1: Operates according to the default.
2) [Network settings] (bit 1)
0: Operates according to [Network settings].
1: Operates according to the default.
4.5 Intelligent Function Module Switch Settings
Description
Mode setting
Default operation setting/battery error detection setting
Response monitoring time setting
For system use (Do not set.)
Normal operation mode
Tests the ROM/RAM/intelligent function module switch settings.
(
Section 4.6.2 Hardware test)
Executes the 10BASE-T/100BASE-TX interface self-diagnostics
test. (
Section 4.6.1 Self-loopback test)
b3
b2
b1
b0
Switch 2
Default operation setting [Account setting]
0: Operates according to [Account setting].
1: Operates according to the default.
User name :QJ71MES96
Password :MITSUBISHI
Default operation setting [Network settings]
0: Operates according to [Network settings].
1: Operates according to the default.
IP ADDRESS:192.168.3.3
Subnet mask:255.255.255.0
Description