Mitsubishi Electric Melsec Q Series User Manual page 370

Programmable contoller mes interface module
Hide thumbs Also See for Melsec Q Series:
Table of Contents

Advertisement

10
TROUBLESHOOTING
Error code
0x20300010
0x20300011
0x20300012
0x20300013
0x20300014
0x20300015
0x20310010
0x20310011
0x20310012
0x20310013
0x20400001
*1
0x20400002
0x20400010
0x20400011
0x20400012
10
- 29
10.2 Error Code List
10.2.2 Error codes of DB Connection Service
Table 10.7 Access log output error list of DB Connection Service
Error description and cause
(SID [Session ID]: Request Receive Error: [IP
address])
Connection disconnected during request reception.
(SID [Session ID]: Request Receive Error: [IP
address])
Timed out during request reception.
(SID [Session ID]: Request Receive Error: [IP
address])
Detected failure of the MES interface module or the
configuration computer while waiting for or
receiving a request.
(SID [Session ID]: Request Receive Error: [IP
address])
Receive I/O error
(SID [Session ID]: Request Receive Error: [IP
address])
Buffer overrun (Request length exceeded)
(SID [Session ID]: Request Receive Error: [IP
address])
Received an invalid request.
(SID [Session ID]: Response Transmit Error: [IP
address])
Failed to transmit a response due to disconnection.
(SID [Session ID]: Response Transmit Error: [IP
address])
Timed out during response transmission
(SID [Session ID]: Response Transmit Error: [IP
address])
Detected failure of the MES interface module or the
configuration computer during response
transmission.
(SID [Session ID]: Response Transmit Error: [IP
address])
Send I/O error
(SID [Session ID]: DB Connect: [Data source]:
[User]: Failed)
Failed in DB connection due to insufficient memory.
(SID [Session ID]: DB Connect: [Data source]:
[User]: Failed)
Failed in DB connection due to insufficient
resources.
(SID [Session ID]: DB Connect: [Data source]:
[User]: Failed)
Invalid DB connection request
System error
(From the previous page)
Corrective action
• Check if it is connected to the network.
• Check if the gateway and/or hub is operating.
• Check if the power of the module is not turned
off.
• Check if the source IP address belongs to the
MES interface module or the configuration
computer.
• Check the version of the MES interface module
or MES Interface Function Configuration Tool.
• Check if it is connected to the network.
• Check if the gateway and/or hub is operating.
• Check if the power of the module is not turned
off.
• Terminate any unnecessary applications.
• Add more memory to the personal computer.
• Check if the source IP address belongs to the
MES interface module or the configuration
computer.
• Check the version of the MES interface module
or MES Interface Function Configuration Tool.
• Please consult your local Mitsubishi
representative.
(To the next page)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Qj71mes96Qj71mes96nSw1dnc-mesif-e

Table of Contents