Selected application templates and functions from the library already bring a predefined set of operational
indications with them which you can adjust individually at any time.
8.4.5.5
Setting-History Log
All individual setting changes and the downloaded files of entire parameter sets are recorded in the log for
setting changes. This enables you to determine setting changes made are associated with events logged (for
example, faults). On the other hand, it is possible to prove with fault analyses, for example, that the current
status of all settings truly corresponds to their status at the time of the fault. Up to 200 indications can be
stored in the setting-history log.
Reading from the PC with DIGSI 5
•
To reach the log for setting changes of your SIPROTEC 5 device, use the project-tree window.
Project → Device → Process Data → Log → Setting changes
The status of the setting-history log last loaded from the device is shown to you.
•
To update (synchronization with the device), click the Read log entries button in the headline of the
indication list
[scparamd-030211-01, 1, en_US]
Figure 8-15
Reading on the Device through the On-Site Operation Panel
•
To reach the setting-history log from the main menu, use the navigation keys of the on-site operation
panel.
Menu → Indications → Setting changes
•
You can navigate within the displayed indication list using the navigation keys (up/down) on the on-site
operation panel.
[schislog-090413-01.tif, 1, en_US]
Figure 8-16
SIPROTEC 5, Operation, Manual
C53000-G5040-C003-7, Edition 06.2016
(Figure
8-15).
Reading the Setting-History Log with DIGSI 5
Reading the Setting-History Log on the On-Site Operation Panel of the Device
Operation in the Operating State
8.4 Indications
125