Expanding Devices

2.2 Surface-Mounting Devices with Integrated On-Site Operation Panel

2.2
Surface-Mounting Devices with Integrated On-Site Operation
Panel

Basic Rules for Expansion

2.2.1
NOTE
i
i
Prepare the following tools for the device expansion:
Phillips screwdriver size PZ1 and PZ2
Screwdriver DIN 4 x 0.8
During assembly, use the prescribed torques
Comply with the following basic rules when extending devices:
Always fit the base module on the right in the 1st device row.
Always fit the expansion modules from right to left.
Always fit the on-site operation panel of the base module on the left.
Always fit the on-site operation panels of the expansion modules from left to right.
Always fit the on-site operation panel of the expansion module with the key switches in the 1st place
next to the on-site operation panel of the base module.
Always fit the on-site operation panels without LEDs last.
Join the on-site operation panels to one another with 2 mounting brackets.
Always install a power-supply module PS203 on the right as the first unit in the 2nd device row.
Please note that the PS203 must always have the same rated voltage as the base module.
In the 2nd device row, you do not need any on-site operation panels, mounting brackets, or distance
frames.
NOTE
i
i
When expanding a device in the 1st device row, order 2 mounting brackets that match the width of the