Table 8-8
Operting Range
Set/operate
Switching (operation)
Switching (unlocked)
Switching authority

Setting Function Settings

8.7.8
Enter the function settings of your SIPROTEC 5 device preferably using the DIGSI 5. You have access here to all
possible settings. Using the on-site operation panel you can make individual setting changes while the device
is in operation.
Offline Settings Using DIGSI 5
To reach the function parameter settings of your SIPROTEC 5 device, use the project-tree window.
Select Project → Device → Parameters → Function group → Function → Function block
The settings of the selected function block are displayed in the main window.
If multiple settings groups (see chapter
that you are making your changes in the correct settings group. You can change this in the header of the main
window if necessary. In another column of the main window, you can compare the setting values with those
in another settings group.
To change a setting value, click the setting arrows of the parameter concerned.
For selection of settings, select a value from the displayed list of possible settings.
For decimal parameters, you can change the setting value incrementally using the setting arrows, or
enter the setting value directly via your PC keyboard. Setting values that are not permitted are indicated
by a red background color and red exclamation marks in the affected areas of the project-tree window.
DIGSI 5 cannot load invalid setting values into the device.
SIPROTEC 5, Operation, Manual
C53000-G5040-C003-7, Edition 06.2016
Default Setting of Confirmation IDs
8.7.9 Settings Group
Default Setting
222222
333333
444444
666666
Switching) have been activated, first make sure
Operation in the Operating State
8.7 Change Device Settings