Maintenance, On-the-Spot Assistance and Test
9.2 Error Search and Correction
Diagnostic Log
Offset failure at a measuring input:
Check for the affected module in the operational log.
If the failure remains, contact the repair service.
A wrong display type was detected.
Contact the repair service.
CPU failure at base module:
Contact the repair service.
Communication-configuration failure:
Reload the DIGSI device configuration.
Update the device firmware or the DIGSI device configuration.
Port E/F/M/N/P: Communication module with incompatible firmware version detected.
Firmware update required.
Clock failure:
Check time setting first.
Change the battery if necessary.
If the failure remains, contact the repair service.
A current terminal is missing.
Check your hardware and the connections!
FPGA hardware failure at the base module:
Contact the repair service.
The device is low on memory. Reduce the number of allocated functions, stages, and/or setting groups in the
configuration.
Configuration error:
The version of one or more functions is incompatible to the used firmware. Load a suitable DIGSI device
configuration.
Failed reading significant feature
Unknown significant feature
Failed reading bay type
Wrong hardware configuration:
Synchronize the hardware configuration of the device and in DIGSI.
Unknown bay type
Failed reading disconnector type
Unknown disconnector type
Maximum number of feeder bays exceeded
Maximum number of coupler bays exceeded
Maximum number of coupler bays with 1 CT exceeded
Maximum number of coupler bays with 2 CT exceeded
Maximum number of coupler bays without CT exceeded
Maximum number of bus section bays exceeded
Maximum number of bus zones exceeded
Maximum number of bus zones without measuring system exceeded
Maximum number of disconnectors exceeded
Maximum number of busbar disconnectors exceeded
Maximum number of line disconnectors to busbar exceeded
Maximum number of line disconnectors exceeded
Maximum number of transfer bus disconnectors exceeded
Maximum number of sectionalizing disconnectors exceeded
Maximum number of level 2 disconnectors exceeded
186