Operation in the Operating State
8.4 Indications
8.4.5.8
Device-Diagnosis Log
The logging and the display of concrete instructions are done in the device-diagnosis log during
•
Required maintenance (for example, battery supervision)
•
Identified hardware defects
•
Compatibility problems
Up to 500 indications can be stored in the device-diagnosis log. In normal operation of the device, it is suffi-
cient for diagnostic purposes to follow the entries of the operational log. This specific significance is assumed
by the device-diagnosis log when the device is no longer ready for operation due to hardware defect or
compatibility problems and the fallback system is active.
Reading from the PC with DIGSI 5 in Normal Operation
•
To reach the device-diagnosis log of your SIPROTEC 5 device, use the project-tree window.
Project → Device → Device Information → Log → Device-diagnosis log
The status of the device-diagnosis log last loaded from the device is shown to you.
•
To update (synchronization with the device) click the button Update in the headline of the indication list.
[scdevdia-140912-01, 1, en_US]
Figure 8-22
Reading on the Device through the On-Site Operation Panel in Normal Operation
•
To reach the diagnosis log from the main menu, use the navigation keys of the on-site operation panel.
Main Menu → Test & Diagnosis → Indications → Device diagnosis
•
You can navigate within the displayed indication list using the navigation keys (up/down) on the on-site
operation panel.
130
Reading the Device-Diagnosis Log with DIGSI 5
SIPROTEC 5, Operation, Manual
C53000-G5040-C003-7, Edition 06.2016