Feedback From The Abb E-Clipse Bypass - Efb - ABB ACH580 Series User Manual

E-clipse bypass and packaged drive
Table of Contents

Advertisement

94
Communications fault
When using fieldbus control, specify the bypass' action if external serial
communication is lost.
Bypass Parameter
3004
3005
Feedback from the ABB E-Clipse Bypass – EFB
Pre-defined feedback
Inputs to the controller (bypass outputs) have pre-defined meanings established by
the protocol. This feedback does not require bypass configuration. The following
table lists a sample of feedback data. For a complete listing, see input word/point/
object listings in the technical data for the appropriate protocol.
0101
Note: As noted above, Modbus provides direct access to all parameters using the
format: 400000 + (group #) * 256 + parameter #.
Example: drive parameter 28.01 is mapped as 40000 + 28 * 256 + 1 = 407169.
Type
DI
DI
DI
DI
DI
DI
DI
DI
DI
DI
Embedded fieldbus
COMM LOSS
0 (Not Sel)
1 (Fault)
2 (Const Sp7)
3 (Last Speed)
COMM FAULT TIME Set time delay before acting on a communication loss.
Bypass Parameter
MOTOR CURR
Name
System Ready
System is ready to accept start command (either
mode).
System Enabled
System is enabled to start motor (either mode).
System Started
System start interlocks are made and start
command has been received (either mode).
Motor runs if run permissive is active.
System Running
Motor is running (either mode).
Fieldbus Local
System is under fieldbus local control (either
mode).
Bypass Fault
Bypass is faulted.
Bypass Warning
Bypass is alarming.
Comm Control
System is configured for control in the comm
channel
Override
Override status
DI1 Status
Bypass digital input 1 status
ACH580 E-Clipse bypass and packaged drive user manual
Value
Set for appropriate drive/bypass response. NOTE:
If the system is in bypass mode when
communication is lost, choices 2 and 3 will cause
the bypass contactor to remain in its present state.
Modbus
400257
Description
Setting
Protocol Reference
N2
BACnet
AI1
AV0
N2
BACnet
BI1
BV7
BI2
BV9
BI3
BV1
BI4
BV0
BI5
N/A
BI6
BV2
BI7
BV5
BI8
N/A
BI9
BV13
BI10
BI5

Hide quick links: