242
Type Code
ACH580-PxR-052A-6
ACH580-PxR-062A-6
ACH580-PxR-077A-6
ACH580-PxR-099A-6
ACH580-PxR-125A-6
ACH580-PxR-144A-6
ACH580-PxR-180A-4
ACH580-PxR-240A-4
1) "PxR" represents both PCR and PDR.
2) PCR is rated 600Y/347V unless otherwise specified. For use on a solidly grounded Wye source only.
3) PCR supports Delta network configuration.

Technical data

Nominal Output
575 Volt
Range
Drive
Current
1, 2
A
3
52
62
77
99
125
144
180
240
ACH580 E-Clipse bypass and packaged drive user manual
Internal Drive
Base
Fuse Rating
Package
Drive
Power
Frame
Size
HP
Class
50
R5
Class T
60
R5
Class T
75
R5
Class T
100
R7
Class T
125
R7
Class T
150
R8
Class T
150
R2
Class T
200
R2
Class T
External Fuse for
Disconnect Option
Current
Max Current
Class
Rating
Rating
80A
N/A
N/A
80A
N/A
N/A
100A
N/A
N/A
150A
N/A
N/A
175A
N/A
N/A
200A
N/A
N/A
300A
N/A
N/A
350A
Class J
400A Max
or RK1