E-Clipse Hvac Default Macro - ABB ACH580 Series User Manual

E-clipse bypass and packaged drive
Table of Contents

Advertisement

52

E-Clipse HVAC Default macro

Speed Reference / Process Setpoint
Process Feedback Signal
Customer Auto Start
Firestat, Freezestat, High Static Switch
Parameter Number
*
Smoke Control (Override1) is a fixed input. Closing Digital Input 6 will place the E-Clipse Bypass in Smoke
Control mode which may reassign the function of the other Digital Inputs. Refer to the Smoke Control
(Override1) documentation.
Application macros
ACH580 E-Clipse bypass and packaged drive user manual
E-Clipse HVAC Default
ACH580 CONTROL BOARD
X1
Terminal for Signal Cable Shield
1
Analog Input 1
2
Analog Input Common
3
10V / 10mA Reference Voltage for Potentiometer
4
Analog Input 2
5
Analog Input Common
6
E-CLIPSE BYPASS CONTROL BOARD
X2
1
+24VDC
2
+24VDC
3
Digital Input Common
4
GND
5
Digital Input 1 (Parameter 1601)
6
Digital Input 2 (Parameter 1602, 06)
7
Digital Input 3 (Parameter 1603)
8
Digital Input 4 (Parameter 1604, 07)
9
Digital Input 5 (Parameter 1605, 1701) NOT SEL
10
(Fixed)
X2
11
Relay Output 1 (Parameter 1401)
12
Default Operation: Bypass Not Faulted 11 connected to 13
13
14
Relay Output 2 (Parameter 1404)
15
Default Operation: System Running
16
17
Relay Output 3 (Parameter 1407)
18
Default Operation: System Started
19
Relay Output 4 (Parameter 1410)
20
21
Default Operation: Bypass Selected
22
Relay Output 5 (Parameter 1413)
23
24
Default Operation: Bypass In Auto
25
Parameters Changed Relative to E-Clipse HVAC Default
Description
START/STOP
NOT SEL
INTERLOCK 1
NOT SEL
SMOKE CONTROL* (Override 1)
BYP NOT FLT
Bypass Faulted 11 connected to 13
SYS RUNNING
14 connected to 16
SYS STARTED
17 connected to 19
BYPASS SEL
20 connected to 22
BYPASS AUTO
23 connected to 25
Setting