ACH580 E-Clipse bypass and packaged drive user manual
Feedback from the drive – EFB
Pre-defined feedback
Inputs to the controller (drive outputs) have pre-defined meanings established by the
protocol. This feedback does not require drive configuration. The following table lists
a sample of feedback data. For a complete listing, see input word/point/object
listings in the technical data for the appropriate protocol starting on page 100.
01.01
01.06
01.07
01.10
01.14
01.11
01.13
01.57
10.02
10.21
58.19
58.19
Note: With Modbus, any parameter can be accessed using the format: 4 followed by
the parameter number. Example: 400000 + (group #) * 256 + parameter#
Drive Parameter
Motor Speed Used
Output Frequency
Motor Current
Motor Torque
Output Power
DC Voltage
Output Voltage
Inverter KWH Counter (resettable)
DI Delayed Status
RO Status
EFB Status Word – bit 0 (STOP)
EFB Status Word – bit 2 (REV)
Protocol Reference
Modbus
N2
400257
AI3
400262
AI1
400263
AI4
400266
AI5
400270
AI6
400267
AI11
400269
AI12
400313
AI8
402562
BI12
402581
BI4, BI5, BI6
414867 bit 0
BI1
414867 bit 2
BI2
89
BACnet
AV0
AV1
AV4
AV5
AV6
AV2
AV3
AV8
BI6
BI0
BV0
BV1
Embedded fieldbus