Smoke Control (Override1) Macro - ABB ACH580 Series User Manual

E-clipse bypass and packaged drive
Table of Contents

Advertisement

ACH580 E-Clipse bypass and packaged drive user manual

Smoke Control (Override1) macro

Speed Reference / Process Setpoint
Process Feedback Signal
Fire Shutdown & Customer Auto Start
Damper End Switch
High Static Switch
Manual Smoke Control & Supply SD
Freezestat & Return SD
Automatic Smoke Control
To Damper Actuator
Parameter Number
1602
1603
1604
1605
*
Smoke Control (Override1) is a fixed input. Closing Digital Input 6 will place the E-Clipse Bypass in Automatic
Smoke Control mode. The Macro change will be implemented when DI6 closes. All Interlock and Permissives
are required before the motor runs. Refer to the Smoke Control (Override1) documentation.
ACH580 CONTROL BOARD
X1
Terminal for Signal Cable Shield
1
Analog Input 1
2
Analog Input Common
3
10V / 10mA Reference Voltage for Potentiometer
4
Analog Input 2
5
Analog Input Common
6
E-CLIPSE BYPASS CONTROL BOARD
X2
1
+24VDC
2
+24VDC
3
Digital Input Common
4
GND
5
Digital Input 1 (Parameter 1601)
6
Digital Input 2 (Parameter 1602)
7
Digital Input 3 (Parameter 1603)
8
Digital Input 4 (Parameter 1604)
9
Digital Input 5 (Parameter 1605)
10
X2
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
Damper End Switch
PERMISSIVE
High Pressure Switch, High Priority Safeties
INTERLOCK 1
Supply Smoke Detector, Emergency Shutdown
INTERLOCK 2
Freezestat, Low Priority Safeties
INTERLOCK 3
START/STOP
RUN PERMISSIVE
INTERLOCK 1
INTERLOCK 2
INTERLOCK 3
(Fixed)
SMOKE CONTROL* (Override 1)
Relay Output 1 (Parameter 1401)
Default Operation: Bypass Not Faulted 11 connected to 13
Bypass Faulted 11 connected to 12
Relay Output 2 (Parameter 1404)
Default Operation: System Running
Relay Output 3 (Parameter 1407)
Default Operation: System Started
Relay Output 4 (Parameter 1410)
Default Operation: Bypass Selected
Relay Output 5 (Parameter 1413)
Default Operation: Bypass In Auto
Description
55
BYP NOT FLT
SYS RUNNING
14 connected to 16
SYS STARTED
17 connected to 19
BYPASS SEL
20 connected to 22
BYPASS AUTO
23 connected to 25
Setting
DI2
DI3
DI4