System overview -
When bypass parameter 1625 COMM CTL = (0) DRIVE ONLY, the drive's BACnet
objects are supported using the drive's device address. The bypass's BACnet
objects related to the control word are no longer valid See
EFB
Bypass BACnet objects not valid
Point #
BV10
BV11
BV12
BV14
BV15
BV16
BV17
BV18
When bypass parameter 1625 COMM CTL = (1) SYSTEM, the drive's BACnet
following objects related to control are no longer available when using the drive's
device address.
Drive BACnet objects not valid
Point #
BV10
BV12
BV20
BV21
Drive overview
Bypass parameter Group 58 defines features used by all Embedded Fieldbus (EFB)
protocols.
Note: The system will function as a master with MAC IDs in the range of 1-127. With
MAC ID settings of 128-254, the drive is in slave only mode.
Changes made to drive parameter Group 58, EFB Protocol, do not take affect until
you perform one of the following:
• Cycle the bypass power OFF and ON, or
• Set bypass parameter 5803 to 0, and then back to a unique MAC ID, or
• Use the ReinitializeDevice service.
Embedded fieldbus
on page 79.
Name
RUN/STOP CMD
OVERRIDE CMD
RUN PERMISSIVE CMD
FAULT RESET
START INTERLOCK 1
START INTERLOCK 2
START INTERLOCK 3
START INTERLOCK 4
Name
RUN/STOP CMD
RUN PERMISSIVE CMD
START INTERLOCK 1
START INTERLOCK 2
ACH580 E-Clipse bypass and packaged drive user manual