ACH580 E-Clipse bypass and packaged drive user manual

Maintenance

Maintenance
Maintenance intervals
If installed in an appropriate environment, the drive requires very little maintenance.
This table lists the routine maintenance intervals recommended by ABB for ACH580
enclosures.
Maintenance
Check/replace hinged
door wall mount
enclosure inlet air filter
Enclosure air filter replacement – UL (NEMA) Type 12 hinged door
wall mount enclosures
Filter material
American Air Filter (358-35-06A-12A)
This procedure applies to drive with input disconnect configurations in UL (NEMA)
Type 12 hinged door wall mount enclosures. This filter is located at the bottom of the
enclosure. Use the following procedure to check and replace filters.
1. On the enclosure, remove the screws holding the filter bracket in place.
2. Remove the filter kit from the enclosure.
Enclosure
Configuration
Hinged door wall
mount UL (NEMA)
Type 12 enclosures
Material
Back of
Mounting
Screws (4X)
Interval
Check every
3 months. Replace
as needed.
Filter Type
POLYKLEON WHITE 12.7mm (1/2 in.) X 152.4mm (6 in.) X
304.6mm (12 in.) stk.
Filter Bracket
Instruction
Enclosure air filter replacement
– UL (NEMA) Type 12 hinged
door wall mount enclosures
page 235.
Enclosure Door
Bottom of Enclosure
Maintenance
235
on