Default Control Connections For The Abb Standard Macro - ABB ACS560 Firmware Manual

General purpose drives
Table of Contents

Advertisement

Default control connections for the ABB standard macro

1...10 kohm
Max.
500 ohm
9)
R3...R8
6)
X1
Reference voltage and analog inputs
1
2
3
4
5
6
7
8
9
X2, X3
Aux. voltage output and programmable digital inputs
8 )
10
11
6)
12
DCOM
13
14
15
16
17
18
X6, X7, X8 Relay outputs
19
20
21
22
23
24
25
26
27
X5
Built-in fieldbus
29
30
31
(Frame R0...R2)
S100
TERM&BIAS
(Frame R3...R8)
S100
S200
Safety torque off
X4
R0...R2 R3...R8
33
-
34
SGND
35
OUT1
36
7)
IN1
6)
37
IN2
X10
24 V AC/DC (frames R6...R8 only)
40
24 V AC/DC- in
41
24 V AC/DC+ in
X11
Redundant auxiliary voltage output (frames R0...R2 only)
42
43
44
DCOM
SCR
Signal cable shield (screen)
External frequency reference:
AI1
1) 4)10)
0...10 V
AGND
Analog input circuit, common
+10V
10 V DC reference voltage
AI2
Not configured
AGND
Analog input circuit, common
Output frequency, 0...20 mA
AO1
see
13.12
Motor current
AO2
see
13.22
AGND
Analog output circuit common
+24V
Aux. voltage output +24 VDC, max. 250 mA
DGND
Aux. voltage output common
Digital input common for all
DI1
Stop (0) / Start (1)
DI2
Forward (0) / reverse (1)
DI3
Constant frequency sel 110)
DI4
Constant frequency sel 2
DI5
Ramp 1 (0) / Ramp 2 (1)
DI6
Not configured
RO1C
RO1A
RO1B
RO2C
RO2A
RO2B
RO3C
RO3A
RO3B
B+
Internal Modbus RTU (EIA-485), see
A-
control through the embedded fieldbus
interface (EFB)
DGND
Termination resistor and bias resistor switch
TERM
Termination resistor switch
BIAS
Bias resistor switch
OUT1
Safety torque off function. Factory connection.
OUT2
Both circuits must be closed for the drive to
SGND
start. See Safe torque off function in the drive
IN1
hardware manual.
IN2
24V AC/DC input, for control unit power supply
when external main power is disconnected.
+24 V
Aux. voltage output +24 V DC, max. 250 mA
DGND
Aux. voltage output common
Digital input common for all
Control macros 103
: see
22.11
2)
11)
:
11)
:
10)
: see
20.03
10)
: see
10)
:
4) 10)
: see
5) 9)
: see
11)
Ready Run
: see
10.24
250 V AC / 30 V DC
2 A
11)
Running
: see
10.27
250 V AC / 30 V DC
2 A
11)
Fault (-1)
: see
10.30
250 V AC / 30 V DC
2 A
3)
20.03
28.23
28.71
Fieldbus
3)

Hide quick links: