26 Start-up, control with I/O and ID run

How to control the drive through the I/O interface

The table below describes how to operate the drive through the digital and analog
inputs when:
• the motor start-up is performed, and
• the default parameter settings of the ABB standard macro are in use.
If you need to change the direction of rotation,
navigate to Menu
make sure that the minimum speed/frequency limit has
a negative value and the maximum speed/frequency
limit has a positive value.
Make sure that the ABB standard macro control connections are correct. See
macro
on page 102.
Make sure that the drive is in remote control. Press key
local control.
In remote control, the panel display shows text Rem at the top left.
Starting and controlling the speed of the motor
Switch on the digital input DI1 on.
Observe the rotating arrow next to Rem. The dotted
arrow appears until the setpoint is reached.
Regulate the drive output frequency (motor speed) by
changing the voltage of analog input AI1.
Changing the direction of the motor rotation
To change the direction, perform as follows
For reverse direction, switch on the digital input
DI2.
For forward direction, switch off the digital input
DI2.
To stop the motor, switch digital input DI1 to off.
Observe that the arrow stops rotating.
Preliminary settings
Motor control
Stopping the motor
and
Max
50.00Hz
Min
-50.00Hz
to switch between remote and
Loc/Rem
Rem
Rem
Rem
Max
50.00Hz
ABB standard
13.4 Hz
13.04
Hz
13.4 Hz
13.04
Hz
0.00 Hz
0.00
Hz