Diagnostics - ABB ACS560 Firmware Manual

General purpose drives
Table of Contents

Advertisement

170 Parameters
No.
Name/Value
04.40
Event word 1
Bit
Name
0
User bit 0
1
User bit 1
...
...
15
User bit 15
0000h...FFFFh
04.41
Event word 1 bit 0
code
0000h...FFFFh
04.43
Event word 1 bit 1
code
0000h...FFFFh
04.45,
...
04,47,
04,49,
...
04.71
Event word 1 bit 15
code
0000h...FFFFh
05

05 Diagnostics

05.01
On-time counter
0...65535 d
05.02
Run-time counter
0...65535 d
05.03
Hours run
0.0...
429496729.5 h
05.04
Fan on-time
counter
0...65535 d
Description
Shows the user-defined event word. This word collects the
status of the events (warnings, faults or pure events) selected
by parameters 04.41...04.71.
This parameter is read-only.
Description
1 = Event selected by parameter
1 = Event selected by parameter
...
1 = Event selected by parameter
User-defined event word.
Selects the hexadecimal code of an event (warning, fault or
pure event) whose status is shown as bit 0 of
word
1. The event codes are listed in chapter
(page 409).
Code of event.
Selects the hexadecimal code of an event (warning, fault or
pure event) whose status is shown as bit 1 of
word
1. The event codes are listed in chapter
(page 409).
Code of event.
...
Selects the hexadecimal code of an event (warning, fault or
pure event) whose status is shown as bit 15 of
word
1. The event codes are listed in chapter
(page 409).
Code of event.
Various run-time-type counters and measurements related to
drive maintenance.
All parameters in this group are read-only unless otherwise
noted.
On-time counter. The counter runs when the drive is
powered.
On-time counter.
Motor run-time counter. The counter runs when the inverter
modulates.
Motor run-time counter.
Corresponding parameter to
hours, that is, 24 *
05.02
Hours.
Running time of the drive cooling fan. Can be reset from the
control panel by keeping Reset down for over 3 seconds.
Cooling fan run-time counter.
04.41
04.43
04.71
04.40 Event
Fault tracing
04.40 Event
Fault tracing
04.40 Event
Fault tracing
05.02 Run-time counter
value + fractional part of a day.
Def/FbEq16
-
is active
is active
is active
1 = 1
0x2310h
1 = 1
0x3210h
1 = 1
...
0x2330h
1 = 1
0
1 = 1 d
0
1 = 1 d
in
-
1 = 1 h
0
1 = 1 d

Hide quick links: