428 Fault tracing
Fault / Aux. code
Code
code visible only on
(hex)
assistant control panel
and drive composer)
5690
PU communication
internal
5691
Measurement circuit
ADC
5692
PU board powerfail
5693
Measurement circuit
DFF
5695
Reduced run
5697
Charging feedback
5698
Unknown PU fault
50A0
Fan
6181
FPGA version
incompatible
6306
FBA A mapping file
6481
Task overload
6487
Stack overflow
64A3
Application loading
(aux
Cause
Internal communication error.
Measurement circuit fault.
Power unit power supply
failure.
Measurement circuit fault.
Configured power units not
found.
Charging feedback signal
missing.
The power unit logic generated
a fault which is not known by
software.
Cooling fan stuck or
disconnected.
Firmware and FPGA versions
are incompatible.
Fieldbus adapter A mapping
file read error.
Internal fault.
Internal fault.
Application file incompatible or
corrupted.
8006 Not enough memory for the
application.
8007 The application contains the
wrong system library version.
8008 The application is empty.
8009 The application contains
invalid tasks.
What to do
Contact your local ABB representative.
Contact your local ABB representative.
Contact your local ABB representative.
Contact your local ABB representative.
Configure the power units.
Check the feedback signal coming from
the charging system
Check the logic and software
compatibility.
Check fan operation and connection.
Replace fan if faulty.
Reboot the control unit (using parameter
96.08 Control board
boot) or by cycling
power. If the problem persists, contact
your local ABB representative
Contact your local ABB representative.
Reboot the control unit (using parameter
96.08 Control board
boot) or by cycling
power. If the problem persists, contact
your local ABB representative
Reboot the control unit (using parameter
96.08 Control board
boot) or by cycling
power. If the problem persists, contact
your local ABB representative.
Check the auxiliary code. See actions for
each code below.
Reduce the size of the application.
Reduce the number of parameter
mappings.
See the drive-specific log generated by
Automation Builder.
Update the system library or reinstall
Automation Builder.
See the drive-specific log generated by
Automation Builder.
In Automation Builder, give a "Clean"
command and reload the application.
In Automation Builder, check application
task configuration, give a "Clean all"
command, and reload the application.