336 Parameters
No.
Name/Value
58.16
Communication
loss time
0.0...6000.0 s
58.17
Transmit delay
0...65535 ms
58.18
EFB control word
0000h...FFFFh
58.19
EFB status word
0000h...FFFFh
58.25
Control profile
ABB Drives
DCU Profile
58.26
EFB ref1 type
Speed or frequency Type and scaling is chosen automatically according to the
Transparent
General
Torque
Speed
Frequency
Description
Sets a timeout for EFB communication. If a communication
break lasts longer than the timeout, the action specified by
parameter
58.14 Communication loss action
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter
Communication control (Refresh
See also parameter
58.15 Communication loss
EFB communication timeout.
Defines a minimum response delay in addition to any fixed
delay imposed by the protocol.
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter
Communication control (Refresh
Minimum response delay.
Displays the raw (unmodified) status word sent by the drive to
the Modbus controller. For debugging purposes.
This parameter is read-only.
Control word sent by Modbus controller to the drive.
Displays the raw (unmodified) status word for debugging
purposes.
This parameter is read-only.
Status word sent by the drive to the Modbus controller.
Defines the communication profile used by the protocol.
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter
Communication control (Refresh
ABB Drives control profile (with a 16-bit control word)
DCU control profile (with a 16 or 32-bit control word)
Selects the type and scaling of reference 1 received through
the embedded fieldbus interface.
The scaled reference is displayed by
currently active operation mode as follows.
Operation mode
(see par. 19.01)
Speed control
Torque control
Frequency control
No scaling is applied.
Generic reference without a specific unit. Scaling: 1 = 100.
Torque reference. The scaling is defined by parameter
Torque
scaling.
Speed reference. The scaling is defined by parameter
Speed
scaling.
Frequency reference. The scaling is defined by parameter
46.02 Frequency
scaling.
is taken.
58.06
settings).
mode.
58.06
settings).
58.06
settings).
03.09 EFB reference
Reference 1 type
Speed
Speed
Frequency
46.03
46.01
Def/FbEq16
3.0 s
1 = 1
3.0 ms
1 = 1
-
1 = 1
-
1 = 1
ABB Drives
0
5
Speed or
frequency
1.
0
1
2
3
4
5