ABB ACS560 Firmware Manual page 261

General purpose drives
Hide thumbs Also See for ACS560:
Table of Contents

Advertisement

No.
Name/Value
31.19
Motor phase loss
No action
Fault
31.22
STO indication
run/stop
Fault/Fault
Fault/Warning
Description
Selects how the drive reacts when a motor phase loss is
detected.
No action taken.
The drive trips on fault
3381 Output phase
Selects which indications are given when one or both Safe
torque off (STO) signals are switched off or lost. The
indications also depend on whether the drive is running or
stopped when this occurs.
The tables at each selection below show the indications
generated with that particular setting.
Notes:
• This parameter does not affect the operation of the STO
function itself. The STO function will operate regardless of
the setting of this parameter: a running drive will stop upon
removal of one or both STO signals, and will not start until
both STO signals are restored and all faults reset.
• The loss of only one STO signal always generates a fault
as it is interpreted as a malfunction.
For more information on the STO, see chapter The Safe
torque off function in the Hardware manual of the drive.
Inputs
Indication (running or stopped)
IN1
IN2
0
0
Faults
0
1
Faults
1
0
1
1
Inputs
IN1
IN2
Running
Fault
5091 Safe torque
0
0
Faults
0
1
torque off
Safe torque off 1
Faults
1
0
torque off
Safe torque off 2
1
1
loss.
Fault
5091 Safe torque off
5091 Safe torque off
FA81 Safe torque off 1
5091 Safe torque off
FA82 Safe torque off 2
(Normal operation)
Indication
Stopped
Warning
off
torque off
5091 Safe
Warning
and
FA81
torque off
FA81 Safe torque off 1
5091 Safe
Warning
and
FA82
torque off
FA82 Safe torque off 2
(Normal operation)
Parameters 261
Def/FbEq16
Fault
0
1
Fault/Fault
0
and
and
1
A5A0 Safe
A5A0 Safe
and fault
A5A0 Safe
and fault

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents