248 Parameters
No.
Name/Value
28.71
Freq ramp set
selection
Acc/Dec time 1
Acc/Dec time 2
DI1
DI2
DI3
DI4
DI5
DI6
FBA A
EFB DCU CW bit
10
Other [bit]
28.72
Freq acceleration
time 1
0.000...1800.000 s
28.73
Freq deceleration
time 1
0.000...1800.000 s
28.74
Freq acceleration
time 2
0.000...1800.000 s
28.75
Freq deceleration
time 2
0.000...1800.000 s
Description
Selects a source that switches between the two sets of
acceleration/deceleration times defined by parameters
28.72...28.75.
0 = Acceleration time 1 and deceleration time 1 are in force
1 = Acceleration time 2 and deceleration time 2 are in force
0
1
Digital input DI1
(10.02 DI delayed
Digital input DI2
(10.02 DI delayed
Digital input DI3
(10.02 DI delayed
Digital input DI4
(10.02 DI delayed
Digital input DI5
(10.02 DI delayed
Digital input DI6
(10.02 DI delayed
Only for the Transparent16 or Transparent32 profile.
Transparent16 or Transparent32 control word bit received
through the fieldbus A interface.
Only for the DCU profile. DCU control word bit 10 received
through the embedded fieldbus interface.
Source selection (see
Terms and abbreviations
Defines acceleration time 1 as the time required for the
frequency to change from zero to the frequency defined by
parameter
46.02 Frequency
been reached, the acceleration continues with the same rate
to the value defined by parameter
If the reference increases faster than the set acceleration
rate, the motor will follow the acceleration rate.
If the reference increases slower than the set acceleration
rate, the motor frequency will follow the reference.
If the acceleration time is set too short, the drive will
automatically prolong the acceleration in order not to exceed
the drive torque limits.
Acceleration time 1.
Defines deceleration time 1 as the time required for the
frequency to change from the frequency defined by
parameter
46.02 Frequency scaling
30.14 Maximum
frequency) to zero.
If there is any doubt about the deceleration time being too
short, ensure that DC overvoltage control
control) is on.
Note: If a short deceleration time is needed for a high inertia
application, the drive should be equipped with braking
equipment such as a brake chopper and brake resistor.
Deceleration time 1.
Defines acceleration time 2. See parameter
acceleration time
1.
Acceleration time 2.
Defines deceleration time 2. See parameter
deceleration time
1.
Deceleration time 2.
status, bit 0)
status, bit 1)
status, bit 2)
status, bit 3)
status, bit 4)
status, bit 5)
on page 162). -
scaling. After this frequency has
30.14 Maximum
frequency.
(not from parameter
(30.30 Overvoltage
28.72 Freq
28.73 Freq
Def/FbEq16
DI5
0
1
2
3
4
5
6
7
18
20
20.000 s
10 = 1 s
20.000 s
10 = 1 s
60.000 s
10 = 1 s
60.000 s
10 = 1 s