ABB ACS560 Firmware Manual page 283

General purpose drives
Table of Contents

Advertisement

No.
Name/Value
PTC analog I/O
PTC AI/DI Voltage
Divider tree
35.12
Temperature 1 fault
limit
-60...5000 °C or
-76...9032 °F or
0...5000 ohm
35.13
Temperature 1
warning limit
-60...5000 °C or
-76...9032 °F or
0...5000 ohm
35.14
Temperature 1 AI
source
Not selected
Description
PTC sensor connected to analog input selected by parameter
35.14 Temperature 1 AI source
The required settings are the same as with selection KTY84
analog I/O.
Note: With this selection, the control program converts the
analog signal to PTC resistance value in ohms and shows it
in parameter
35.02
The parameter name and unit still refer to
temperature.
PTC sensor connected to the analog input selected by
parameter
35.14 Temperature 1 AI
divider connection must be in use instead of the normal PTC
connection. The voltage divider connection uses the
terminals +10 V, digital input and analog input. See the drive
hardware manual for the actual connection.
This selection makes it possible to connect the PTC when no
analog output is available.
The required settings are same as with selection
analog
I/O.
Notes:
• This is applicable only for frames R0...R2.
• Make sure that the digital input that you connect to this
voltage divider circuit is not used for any other purpose in
the control program.
• With this selection, the parameter
resistance in ohms, not motor temperature even the
parameter name and unit still refer to temperature.
Defines the fault limit for temperature supervision function 1.
When measured temperature 1 exceeds the limit, the drive
trips on fault
4981 External temperature
The unit is selected by parameter
Fault limit for temperature monitoring function 1.
Note: If the measured temperature source selection (35.11) is
PTC analog I/O or PTC AI/DI Voltage divider tree, the motor
thermal protection function converts the analog input signal
(35.14) to PTC resistance value (ohms). Also this limit is then
a resistance value even the parameter name and unit refer to
motor temperature (°C or °F). You cannot change the unit to
ohm by the time being (96.16).
Defines the warning limit for temperature supervision
function 1. When measured temperature 1 exceeds the limit,
warning
A491 External temperature 1
The unit is selected by parameter
Warning limit for temperature monitoring function 1.
Note: If the measured temperature source selection (35.11) is
PTC analog I/O or PTC AI/DI Voltage divider tree, the motor
thermal protection function converts the analog input signal
(35.14) to PTC resistance value (ohms). Also this limit is then
a resistance value even the parameter name and unit refer to
motor temperature (°C or °F). You cannot change the unit to
ohm by the time being (96.16).
Specifies the analog input when the setting of
Temperature 1 source
requires measurement through an
analog input.
None.
Parameters 283
and an analog output.
source. A special voltage
KTY84
35.02
shows PTC
1.
96.16 Unit
selection.
is generated.
96.16 Unit
selection.
35.11
Def/FbEq16
20
23
130 °C or
266°F or
4500 ohm
1 = 1 unit
110°C or
230°F or
4000 ohm
1 = 1 unit
Not selected
0