284 Parameters
No.
Name/Value
AI1 actual value
AI2 actual value
Other
35.21
Temperature 2
source
Disabled
Estimated
temperature
KTY84 analog I/O
1 × Pt100 analog
I/O
2 × Pt100 analog
I/O
3 × Pt100 analog
I/O
Description
Analog input AI1 on the control unit.
Analog input AI2 on the control unit.
Source selection (see
Terms and abbreviations
Selects the source from which measured temperature 2 is
read.
Usually this source is from a sensor connected to the motor
controlled by the drive, but it could be used to measure and
monitor a temperature from other parts of the process as long
as a suitable sensor is used as per the selection list.
None. Temperature monitoring function 2 is disabled.
Estimated motor temperature (see parameter
estimated
temperature).
The temperature is estimated from an internal drive
calculation. It is important to set up the ambient temperature
of the motor in
35.50 Motor ambient
KTY84 sensor connected to the analog input selected by
parameter
35.24 Temperature 2 AI source
output.
The following settings are required:
• Set the appropriate analog input unit selection parameter
in group
12 Standard AI
• In parameter group
12 Standard
selection parameter of the analog output to
excitation.
The analog output feeds a constant current through the
sensor. As the resistance of the sensor increases along with
its temperature, the voltage over the sensor increases. The
voltage is read by the analog input and converted into
degrees.
Pt100 sensor connected to a standard analog input selected
by parameter
35.24 Temperature 2 AI source
output.
The following settings are required:
• Set the hardware jumper or switch related to the analog
input to U (voltage). Any change must be validated by a
control unit reboot.
• Set the appropriate analog input unit selection parameter
in group
12 Standard AI
• In parameter group
13 Standard
selection parameter of the analog output to
excitation.
The analog output feeds a constant current through the
sensor. As the resistance of the sensor increases along with
its temperature, the voltage over the sensor increases. The
voltage is read by the analog input and converted into
degrees.
As selection
1 × Pt100 analog
connected in series. Using multiple sensors improves
measurement accuracy significantly.
As selection
1 × Pt100 analog
connected in series. Using multiple sensors improves
measurement accuracy significantly.
on page 162). -
35.01 Motor
temperature.
and an analog
to V (volt).
AI, set the source
Temp sensor 2
and an analog
to
V
(volt).
AO, set the source
Temp sensor 2
I/O, but with two sensors
I/O, but with three sensors
Def/FbEq16
1
2
Estimated
temperature
0
1
2
5
6
7