ABB ACS560 Firmware Manual page 357

General purpose drives
Table of Contents

Advertisement

No.
Name/Value
Clear all
Reset home view
Reset end user
texts
All to factory
defaults
96.07
Parameter save
manually
Done
Save
96.08
Control board boot
No action
Reboot
96.10
User set status
n/a
Loading
Saving
Faulted
User1 IO active
User2 IO active
Description
Restores all editable parameter values to default values,
except
• end user texts, such as customized warnings and faults,
and the drive name
• control macro selection and the parameter defaults
implemented by it
• parameter
95.20 HW options word 1
defaults implemented by it
• group
49 Panel port communication
Restores the home view layout back to show the values of the
default parameters defined by the control macro in use
Restores all end user texts to default values, including the
drive name, contact info, customized fault and warning texts
and currency unit.
Note: PID unit is reset only if it is user editable text, that is,
parameter
40.79 Set 1 units
Restores all drive parameters and settings back to initial
factory values, except
• parameter 95.20 HW options word 1 and the differentiated
defaults implemented by it.
Saves the valid parameter values to the permanent memory
on the drive control unit to ensure that operation can continue
after cycling the power. Save the parameters with this
parameter
• to store values sent from the fieldbus
• when using external +24 V DC power supply to the control
unit: to save parameter changes before you power down
the control unit. The supply has a very short hold-up time
when powered off.
Note: A new parameter value is saved automatically when
changed from the PC tool or control panel but not when
altered through a fieldbus adapter connection.
Save completed.
Save in progress.
Changing the value of this parameter to 1 reboots the control
unit (without requiring a power off/on cycle of the complete
drive module).
The value reverts to 0 automatically.
1 = No action.
1 = Reboot the control unit.
Shows the status of the user parameter sets.
This parameter is read-only.
See also section
User parameter sets
No user parameter sets have been saved.
A user set is being loaded.
A user set is being saved.
Invalid or empty parameter set.
User set 1 has been selected by parameters
I/O mode in1
and
96.13 User set I/O mode
User set 2 has been selected by parameters
I/O mode in1
and
96.13 User set I/O mode
and the differentiated
parameters.
is set to User text.
(page 95).
96.12 User set
in2.
96.12 User set
in2.
Parameters 357
Def/FbEq16
62
512
1024
34560
Done
0
1
No action
0
1
n/a
0
1
2
3
4
5