ABB ACS560 Firmware Manual page 275

General purpose drives
Table of Contents

Advertisement

No.
Name/Value
34.11
Timer 1
configuration
Bit
Name
0
Monday
1
Tuesday
2
Wednesday
3
Thursday
4
Friday
5
Saturday
6
Sunday
7
Season 1
8
Season 2
9
Season 3
10
Season 4
11
Exceptions
12
Holidays
13
Workdays
14...15 Reserved
0b0000...0b1111
34.12
Timer 1 start time
00:00:00...23:59:59 Daily start time of the timer.
34.13
Timer 1 duration
00 00:00...07 00:00 Timer duration.
34.14
Timer 2
configuration
34.15
Timer 2 start time
34.16
Timer 2 duration
34.17
Timer 3
configuration
Description
Defines when timer 1 is active.
Description
1 = Monday is an active start day.
1 = Tuesday is an active start day.
1 = Wednesday is an active start day.
1 = Thursday is an active start day.
1 = Friday is an active start day.
1 = Saturday is an active start day.
1 = Sunday is an active start day.
1 = Timer is active in season 1.
1 = Timer is active in season 2.
1 = Timer is active in season 3.
1 = Timer is active in season 4.
0 = Exceptions days are disabled.
1 = Exception days are enabled. Bits 12 and 13 are taken
into account.
0 = Timer is inactive on exception days configured as
"Holiday".
1 = Timer is active on exception days configured as
"Holiday".
0 = Timer is inactive on exception days configured as
"Workday".
1 = Timer is active on exception days configured as
"Workday".
Configuration of timer 1.
Defines the daily start time of timer 1. The time can be
changed in second steps.
The timer can be started at an other time than the start time.
E.g. if the timer's duration is more than one day and the active
session starts during the time, the timer is started at 00:00
and stopped when there is no duration left.
Defines the duration of timer 1. The duration can be changed
in minute steps.
The duration can extend over the change of the day but if an
exception day becomes active, the period is interrupted at
midnight. In the same way the period started on an exception
day stays active only until the end of the day, even if the
duration is longer. The timer will continue after a break if there
is duration left.
See
34.11 Timer 1
configuration.
See
34.12 Timer 1 start
See
34.13 Timer 1
duration.
See
34.11 Timer 1
configuration.
time.
Parameters 275
Def/FbEq16
0b0111
1 = 1
00:00:00
1 = 1
00 00:00
1 = 1
0b0111
00:00:00
00 00:00
0b0111