296 Parameters
No.
Name/Value
40.06
Process PID status
word
Bit
Name
0
PID active
1
Setpoint frozen
2
Output frozen
3
PID sleep mode
4
Sleep boost
5
Trim mode
6
Tracking mode
7
Output limit high
8
Output limit low
9
Deadband active
10
PID set
11
Reserved
12
Internal setpoint
active
13...15 Reserved
0b0000...0b1111
40.07
Process PID
operation mode
Off
On
On when drive
running
40.08
Set 1 feedback 1
source
Not selected
AI1 scaled
AI2 scaled
Freq in scaled
AI1 percent
AI2 percent
Feedback data
storage
Other
40.09
Set 1 feedback 2
source
40.10
Set 1 feedback
function
In1
Description
Displays status information on process PID control.
This parameter is read-only.
Value
1 = Process PID control active.
1 = Process PID setpoint frozen.
1 = Process PID controller output frozen.
1 = Sleep mode active.
1 = Sleep boost active.
1 = Trim mode active
1 = Tracking function active.
1 = PID output is being limited by par. 40.37.
1 = PID output is being limited by par. 40.36.
1 = Deadband active (see parameter 40.39)
0 = Parameter set 1 in use. 1 = Parameter set 2 in use.
1 = Internal setpoint active (see par. 40.16...40.23)
Process PID control status word.
Activates/deactivates process PID control.
Note: Process PID control is only available in external
control; see section
Local control vs. external control
33).
Process PID control inactive.
Process PID control active.
Process PID control is active when the drive is running.
Selects the primary source of process feedback. See the
control chain diagram on page 495.
None.
12.12 AI1 scaled value
12.22 AI2 scaled value
11.39 Freq in 1 scaled value
12.101 AI1 percent value
12.102 AI2 percent value
40.91 Feedback data storage
Source selection (see
Terms and abbreviations
Selects the second source of process feedback. The second
source is used only if the setpoint function requires two
inputs.
For the selections, see parameter
source.
Defines how process feedback is calculated from the two
feedback sources selected by parameters
feedback 1 source
and
Source 1.
(see page 189).
(see page 191).
(see page 187).
(see page 192)
(see page 192)
(see page 309),
40.08 Set 1 feedback 1
40.08 Set 1
40.09 Set 1 feedback 2
Def/FbEq16
0b0000
1 = 1
Off
(page
0
1
2
AI2 percent
0
1
2
3
8
9
10
on page 162). -
Not selected
In1
source.
0