ABB ACS560 Firmware Manual page 434

General purpose drives
Table of Contents

Advertisement

434 Fault tracing
Fault / Aux. code
Code
code visible only on
(hex)
assistant control panel
and drive composer)
80B4
Signal supervision 5
(Editable message text)
Programmable fault:
32.46 Supervision 5 action
80B5
Signal supervision 6
(Editable message text)
Programmable fault:
32.56 Supervision 6 action
9081
External fault 1
(Editable message text)
Programmable fault:
External event 1 source
31.02 External event 1
type
9082
External fault 2
(Editable message text)
Programmable fault:
External event 2 source
31.04 External event 2
type
9083
External fault 3
(Editable message text)
Programmable fault:
External event 3 source
31.06 External event 3
type
9084
External fault 4
(Editable message text)
Programmable fault:
External event 4 source
31.08 External event 4
type
9085
External fault 5
(Editable message text)
Programmable fault:
External event 5 source
31.10 External event 5
type
A2A1
Current calibration
FA81
Safe torque off 1
FA82
Safe torque off 2
(aux
Cause
Fault generated by the signal
supervision function 5.
Fault generated by the signal
supervision function 6.
Fault in external device 1.
31.01
Fault in external device 2.
31.03
Fault in external device 3.
31.05
Fault in external device 4.
31.07
Fault in external device 5.
31.09
Current offset and gain
measurement calibration will
occur at next start.
Safe torque off function is
active, ie. STO circuit 1 is
broken.
Safe torque off function is
active, ie. STO circuit 2 is
broken.
What to do
Check the source of the fault (parameter
32.47 Supervision 5
signal).
Check the source of the fault (parameter
32.57 Supervision 6
signal).
Check the external device.
Check setting of parameter
External event 1
source.
Check the external device.
Check setting of parameter
External event 2
source.
Check the external device.
Check setting of parameter
External event 3
source.
Check the external device.
Check setting of parameter
External event 4
source.
Check the external device.
Check setting of parameter
External event 5
source.
Informative warning. (See parameter
99.13 ID run
requested).
Check safety circuit connections. For
more information, see chapter The Safe
torque off function in the Hardware
manual of the drive and description of
parameter
31.22 STO indication run/stop
(page 261).
Check the value of parameter
Control board
supply.
31.01
31.03
31.05
31.07
31.09
95.04

Hide quick links: