No.
Name/Value
Override speed/freq Parameter
Motor
potentiometer
Stop
Process PID set 1
70.05
Override direction
Forward
Reverse
DI1
DI2
DI3
DI4
DI5
DI6
-DI1
-DI2
-DI3
-DI4
-DI5
-DI6
Other [bit]
70.06
Override frequency
-500.0...500.0 Hz
70.07
Override speed
-30000.0...
30000.0 rpm
70.20
Override fault
handling
Fault on high
priority
Description
70.06 Override frequency/ 70.07 Override speed
is used as the reference.
22.80 Motor potentiometer ref act
potentiometer)
The output of the drive is shut off and the motor no longer
runs. Override is displayed on the panel but the motor does
not run. Drive follows the specified stop type.
Output of the process PID Set 1 (40.96) is used as the
reference.
Selects the source of the motor direction used in the override
mode.
Direction is forward.
Direction is reverse.
Digital input DI1
(10.02 DI delayed
Digital input DI2
(10.02 DI delayed
Digital input DI3
(10.02 DI delayed
Digital input DI4
(10.02 DI delayed
Digital input DI5
(10.02 DI delayed
Digital input DI6
(10.02 DI delayed
Digital input DI1
(10.02 DI delayed
Digital input DI2
(10.02 DI delayed
Digital input DI3
(10.02 DI delayed
Digital input DI4
(10.02 DI delayed
Digital input DI5
(10.02 DI delayed
Digital input DI6
(10.02 DI delayed
Source selection (see
Terms and abbreviations
Defines the frequency used as reference in the override
mode if
70.04 Override reference source
speed/freq
and the drive is in frequency mode..
Override frequency.
Defines the speed used as reference in the override mode if
70.04 Override reference source
and the drive is in speed mode.
Override speed.
Faults are grouped into high priority faults and low priority
faults. The following faults are high priority, and they are
displayed and they will stop the drive:
2310
Overcurrent,
2340 Short
overvoltage,
4981 External temperature
temperature
2,
5090 STO hardware
off,
FA81 Safe torque off
Other faults are low priority faults. Active low priority faults are
reset when the drive enters override mode. Low priority faults
are ignored when the drive is in override mode.
Fault on high priority faults. The fault must be reset from the
control panel or from a digital input.
(output of the Motor
status, bit 0).
status, bit 1).
status, bit 2).
status, bit 3).
status, bit 4).
status, bit 5).
status, bit 0).
status, bit 1).
status, bit 2).
status, bit 3).
status, bit 4).
status, bit 5).
on page 162). -
is set to
is set to
Override speed/freq
circuit,
3210 DC link
1,
4982 External
failure,
5091 Safe torque
1,
FA81 Safe torque off
Parameters 341
Def/FbEq16
3
4
5
6
Forward
0
1
2
3
4
5
6
7
8
9
10
11
12
13
0.0 Hz
Override
1 = 1 Hz
0.0 rpm
1 = 1 rpm
Fault on high
priority
2.
0