354 Parameters
No.
Name/Value
95.20
HW options word 1
Bit
Name
0
Supply frequency
60 Hz
1...12
Reserved
13
du/dt filter
activation
14...15 Reserved
0b0000...0b1111
95.21
HW options word 2
Bit
Name
0...4
Reserved
5
Bypass present
6
Cabinet drive
7
Reserved
8...15
Reserved
0b0000...0b1111
95.200 Cooling fan mode
Auto
Always on
96

96 System

96.01
Language
Not selected
Description
Specifies hardware-related options that require differentiated
parameter defaults.
This parameter is not affected by a parameter restore.
Value
If you change the value of this bit, you have to do a complete reset to
the drive after the change. After reset you have to reselect the macro
to be used.
See section
Differences in the default values between 50 Hz and
60 Hz supply frequency settings
1 = 60 Hz.
When active, an external du/dt filter is connected to the drive/inverter
output. The setting will limit the output switching frequency, and
force the fan of the drive/inverter module to full speed.
0 = du/dt filter inactive.
1 = du/dt filter active.
Hardware options configuration word.
Specifies more hardware-related options that require
differentiated parameter defaults. See parameter
options word
2.
WARNING! An incorrect setting may cause the motor
to rush uncontrollably, or the brake chopper or resistor
to overload.
Value
1 = Bypass is used.
0 = Inactive, 1 = Active. Only for drive frames R6 or larger.
0 = Inactive, 1 = Active. Only for drive frames R6 or larger.
Hardware options configuration word.
Selects the fan control type. The fan control functionality
enables heat dissipation from the drive and avoids dust
accumulation in the drive.
Controls the fan automatically according to the temperature
changes of the drive.
Fan runs continuously with the maximum speed (50Hz).
Language selection; access levels; macro selection;
parameter save and restore; control unit reboot; user
parameter sets; unit selection.
Selects the language of the parameter interface and other
displayed information when viewed on the control panel.
Notes:
• Not all languages listed below are necessarily supported.
• This parameter does not affect the languages visible in the
Drive composer PC tool. (Those are specified under View
– Settings – Drive default language.)
None.
Def/FbEq16
0b0000
on page 371.0 = 50 Hz.
1 = 1
0b0000
95.20 HW
1 = 1
Auto
0
1
Not selected