ABB ACS560 Firmware Manual page 166

General purpose drives
Table of Contents

Advertisement

166 Parameters
No.
Name/Value
01.14
Output power
-32768.00...
32767.00 kW
01.15
Output power % of
motor nom
-300.00... 300.00%
01.16
Output power % of
drive nom
-300.00... 300.00%
01.17
Motor shaft power
-32768.00...
32767.00 hp or kW
01.18
Inverter GWh
counter
0...65535 GWh
01.19
Inverter MWh
counter
0...1000 MWh
01.20
Inverter kWh
counter
0...1000 kWh
01.24
Flux actual %
0...200%
01.30
Nominal torque
scale
0.000...4000000
N·m or lb·ft
01.31
Ambient
temperature
°C or °F
01.50
Current hour kWh
0.00... 1000000.00
kWh
Description
Drive output power. A filter time constant for this signal can
be defined by parameter
Output power.
Output power in percent of the nominal motor power.
Output power.
Output power in percent of the nominal drive power.
Output power.
Estimated mechanical power at motor shaft. The unit is
selected by parameter
96.16 Unit
Motor shaft power.
Amount of energy that has passed through the drive (in either
direction) in full gigawatt-hours. The minimum value is zero.
Energy in GWh.
Amount of energy that has passed through the drive (in either
direction) in full megawatt-hours. Whenever the counter rolls
over,
01.18 Inverter GWh counter
minimum value is zero.
Energy in MWh.
Amount of energy that has passed through the drive (in either
direction) in full kilowatt-hours. Whenever the counter rolls
over,
01.19 Inverter MWh counter
minimum value is zero.
Energy in kWh.
Used flux reference in percent of nominal flux of motor.
Flux reference.
Torque that corresponds to 100% of nominal motor torque.
The unit is selected by parameter
Note: This value is copied from parameter
nominal torque
if entered. Otherwise the value is calculated
from other motor data.
Nominal torque.
Ambient temperature of the drive.
Note: This parameter is applicable only for frames R6 or
larger.
Temperature
Current hour energy consumption. This is the energy of the
last 60 minutes (not necessarily continuous) the drive has
been running, not the energy of a calendar hour. The value is
set to the value before the power cycle when the drive is
again up and running.
Energy.
46.14 Filter time
power.
selection.
is incremented. The
is incremented. The
96.16 Unit
selection.
99.12 Motor
Def/FbEq16
-
See par.
46.04
-
1 = 1%
-
1 = 1%
-
See par.
46.04
-
1 = 1 GWh
-
1 = 1 MWh
-
10 = 1 kWh
-
1 = 1%
-
1 = 100 unit
-
1 = 1 °
-
1 = 1 kWh