Process Pid Set 1 - ABB ACS560 Firmware Manual

General purpose drives
Hide thumbs Also See for ACS560:
Table of Contents

Advertisement

No.
Name/Value
37.42
ULC underload
timer
0.0...10000.0 s
40

40 Process PID set 1

40.01
Process PID output
actual
-200000.00...
200000.00
40.02
Process PID
feedback actual
-200000.00...
200000.00
40.03
Process PID
setpoint actual
-200000.00...
200000.00
40.04
Process PID
deviation actual
-200000.00...
200000.00
40.05
Process PID trim
output act
-32768...32767
Description
Defines the time period for which time the monitored signal
must remain continuously below the underload curve.
Time.
Parameter values for process PID control.
The drive output can be controlled by the process PID. When
the process PID control is enabled, the drive controls the
process feedback to the reference value.
Two different parameter sets can be defined for the process
PID. One parameter set is in use at a time. The first set is
made up of parameters 40.07...40.50, the second set is
defined by the parameters in group
The binary source that defines which set is used is selected
by parameter
40.57 PID set1/set2
See also the control chain diagrams on pages
Displays the output of the process PID controller. See the
control chain diagram on page 498.
This parameter is read-only.
Process PID controller output.
Displays the value of process feedback after source
selection, mathematical function (parameter
feedback
function), and filtering. See the control chain
diagram on page 495.
This parameter is read-only.
Process feedback.
Displays the value of process PID setpoint after source
selection, mathematical function
function), limitation and ramping. See the control chain
diagram on page 495.
This parameter is read-only.
Setpoint for process PID controller.
Displays the process PID deviation. By default, this value
equals setpoint - feedback, but deviation can be inverted by
parameter
40.31 Set 1 deviation
chain diagram on page 498.
This parameter is read-only.
PID deviation.
Displays the trimmed reference output.
This parameter is read-only.
Trimmed reference.
Parameters 295
41 Process PID set
2.
selection.
495
and 498.
40.10 Set 1
(40.18 Set 1 setpoint
inversion. See the control
Def/FbEq16
20.0 s
1 = 1 s
-
1 = 1
-
1 = 1
-
1 = 1
-
1 = 1
-
1 = 1 unit