Status Word; Status Word For The Abb Drives Profile - ABB ACS560 Firmware Manual

General purpose drives
Hide thumbs Also See for ACS560:
Table of Contents

Advertisement

Fieldbus control through the embedded fieldbus interface (EFB) 451

Status Word

Status Word for the ABB Drives profile

The table below shows the fieldbus Status Word for the ABB Drives control profile.
The embedded fieldbus interface converts the drive Status Word into this form for the
fieldbus. The upper case boldface text refers to the states shown in
diagram for the ABB Drives profile
Bit
Name
0
RDY_ON
1
RDY_RUN
2
RDY_REF
3
TRIPPED
4
OFF_2_STATUS
5
OFF_3_STATUS
6
SWC_ON_
INHIB
7
ALARM
8
AT_
SETPOINT
9
REMOTE
10
ABOVE_
LIMIT
11
USER_0
12
USER_1
13
USER_2
14
USER_3
15
Reserved
on page 454.
Value
STATE/Description
1
READY TO SWITCH ON.
0
NOT READY TO SWITCH ON.
1
READY TO OPERATE.
0
OFF1 ACTIVE.
1
OPERATION D.
0
OPERATION INHIBITED.
1
FAULT.
0
No fault.
1
OFF2 inactive.
0
OFF2 ACTIVE.
1
OFF3 inactive.
0
OFF3 ACTIVE.
1
SWITCH-ON INHIBITED.
0
1
Warning/Alarm.
0
No warning/alarm.
1
OPERATING. Actual value equals Reference (is within
tolerance limits, e.g. in speed control, speed error is
10% max. of nominal motor speed).
0
Actual value differs from Reference (is outside
tolerance limits).
1
Drive control location: REMOTE (EXT1 or EXT2).
0
Drive control location: LOCAL.
1
Actual frequency or speed equals or exceeds
supervision limit (set by drive parameter). Valid in both
directions of rotation.
0
Actual frequency or speed within supervision limit.
Status bits that can be combined with drive logic for
application-specific functionality.
State transition