ABB ACS560 Firmware Manual page 415

General purpose drives
Table of Contents

Advertisement

Warning / Aux. code
(aux code visible only
Code
on assistant control
(hex)
panel and drive
composer)
A590
Drive HW initialization.
A591
Drive HW initialization
A5A0
Safe torque off
Programmable
warning:
31.22 STO
indication run/stop
A5EA
Measurement circuit
temperature
A5EB
PU board powerfail
A5ED Measurement circuit
ADC
A5EE
Measurement circuit
DFF
A5EF
PU state feedback
A5F0
Charging feedback
A5F1
Redundant
measurement
A5F2
Overtemperature hw
A682
Flash erase speed
A684
Power fail saving
Cause
Drive hardware setup is
initializing.
1 - Initializing HW settings for
the first time.
Initialization of the drive
hardware.
0000 Drive hardware setup is
initializing.
0001 Initializing HW settings for the
first time.
Safe torque off function is
active, ie safety circuit signal(s)
connected to connector STO is
lost.
Problem with internal
temperature measurement of
the drive.
Power unit power supply
failure.
Measurement circuit fault.
Measurement circuit fault.
State feedback from output
phases does not match control
signals.
Charging feedback signal
missing.
Duplicated measurements are
beyond limits.
Excessive hardware
temperature.
The flash memory (in the
memory unit) has been erased
too frequently, compromising
the lifetime of the memory.
Power fail saving warning.
Fault tracing 415
What to do
See auxiliary code.
Check the auxiliary code. See actions for
each code below.
Wait for the setup to initialize.
Wait for the setup to initialize.
Check safety circuit connections. For
more information, chapter The Safe
torque off function in the Hardware
manual of the drive and description of
parameter
31.22 STO indication run/stop
(page 261).
Check the value of parameter
Control board
supply.
Contact your local ABB representative.
Contact your local ABB representative.
Contact your local ABB representative.
Contact your local ABB representative.
Contact your local ABB representative.
Check the feedback signal coming from
the charging system.
Contact your local ABB representative.
Contact your local ABB representative.
Avoid forcing unnecessary parameter
saves by parameter
96.07 Parameter
save manually
or cyclic parameter writes
(such as user logger
triggering through parameters).
Check the auxiliary code (format XYYY
YZZZ). "X" specifies the source of
warning (1: generic flash erase
supervision). "ZZZ" specifies the flash
subsector number that generated the
warning.
Contact your local ABB representative.
95.04