ABB ACS560 Firmware Manual page 305

General purpose drives
Table of Contents

Advertisement

No.
Name/Value
AI2 scaled
FB A ref1
FB A ref2
Other
40.51
Set 1 trim mode
Off
Direct
Proportional
Combined
40.52
Set 1 trim selection
Torque
Speed
Frequency
40.53
Set 1 trimmed ref
pointer
Not selected
AI1 scaled
AI2 scaled
FBA ref1
FBA ref2
Other
40.54
Set 1 trim mix
0.000...1.000
40.55
Set 1 trim adjust
-100.000...100.000
40.56
Set 1 trim source
PID ref
Description
12.22 AI2 scaled value
(see page 191).
03.05 FB A reference 1
03.06 FB A reference 2
Source selection (see
Terms and abbreviations
Activates the trim function and selects between direct and
proportional trimming (or a combination of both). With
trimming, it is possible to apply a corrective factor to the drive
reference (setpoint). The output after trimming is available as
parameter
40.05 Process PID trim output act
The trim function is inactive.
The trim function is active. The trimming factor is relative to
the maximum speed, torque or frequency; the selection
between these is made by parameter
selection.
The trim function is active. The trimming factor is relative to
the reference selected by parameter
pointer.
The trim function is active. The trimming factor is a
combination of both
Direct
proportions of each are defined by parameter
mix.
Selects whether trimming is used for correcting the speed,
torque or frequency reference.
Torque reference trimming.
Speed reference trimming.
Frequency reference trimming.
Selects the signal source for the trim reference.
None.
12.12 AI1 scaled value
(see page 189).
12.22 AI2 scaled value
(see page 191).
03.05 FB A reference 1
03.06 FB A reference 2
Source selection (see
Terms and
When parameter
40.51 Set 1 trim mode
defines the effect of direct and proportional trim sources in the
final trimming factor.
0.000 = 100% proportional
0.500 = 50% proportional, 50% direct
1.000 = 100% direct
Trim mix.
Defines a multiplier for the trimming factor. This value is
multiplied by the result of parameter
Consequently, the result of the multiplication is used to
multiply the result of parameter
Multiplier for trimming factor.
Selects the reference to be trimmed.
PID setpoint.
(see page 168).
(see page 168).
on page 162). -
.
40.52 Set 1 trim
40.53 Set 1 trimmed ref
and
Proportional
modes; the
40.54 Set 1 trim
(see page 168).
(see page 168).
abbreviations).
is set to Combined,
40.51 Set 1 trim
40.56 Set 1 trim
Parameters 305
Def/FbEq16
2
3
4
Off
0
1
2
3
Speed
1
2
3
Not selected
0
1
2
3
4
-
0.000
1 = 1
1.000
mode.
adjust.
1 = 1
PID output
1