304 Parameters
No.
Name/Value
40.45
Set 1 sleep boost
time
0.0...3600.0 s
40.46
Set 1 sleep boost
step
0.0...200000.0
40.47
Set 1 wake-up
deviation
-200000.00...
200000.00
40.48
Set 1 wake-up
delay
0.00...60.00 s
40.49
Set 1 tracking mode
Not selected
Selected
DI1
DI2
DI3
DI4
DI5
DI6
Timed function 1
Timed function 2
Timed function 3
Supervision 1
Supervision 2
Supervision 3
Other [bit]
40.50
Set 1 tracking ref
selection
Not selected
AI1 scaled
Description
Defines a boost time for the sleep boost step. See parameter
40.46 Set 1 sleep boost
Sleep boost time.
When the drive is entering sleep mode, the process setpoint
is increased by this value for the time defined by parameter
40.45 Set 1 sleep boost
If active, sleep boost is aborted when the drive wakes up.
Sleep boost step.
Defines the wake-up level as deviation between process
setpoint and feedback.
When the deviation exceeds the value of this parameter, and
remains there for the duration of the wake-up delay
Set 1 wake-up
delay), the drive wakes up.
See also parameter
40.31 Set 1 deviation
Wake-up level (as deviation between process setpoint and
feedback).
Defines a wake-up delay for the sleep function to prevent
nuisance wake-ups. See parameter
deviation.
The delay timer starts when the deviation exceeds the wake-
up level
(40.47 Set 1 wake-up
deviation falls below the wake-up level.
Wake-up delay.
Activates (or selects a source that activates) tracking mode.
In tracking mode, the value selected by parameter
1 tracking ref selection
is substituted for the PID controller
output. See also section
1 = Tracking mode enabled
0.
1.
Digital input DI1
(10.02 DI delayed
Digital input DI2
(10.02 DI delayed
Digital input DI3
(10.02 DI delayed
Digital input DI4
(10.02 DI delayed
Digital input DI5
(10.02 DI delayed
Digital input DI6
(10.02 DI delayed
Bit 0 of
34.01 Timed functions status
Bit 1 of
34.01 Timed functions status
Bit 2 of
34.01 Timed functions status
Bit 0 of
32.01 Supervision status
Bit 1 of
32.01 Supervision status
Bit 2 of
32.01 Supervision status
Source selection (see
Terms and abbreviations
Selects the value source for tracking mode. See parameter
40.49 Set 1 tracking
mode.
None.
12.12 AI1 scaled value
step.
time.
inversion.
40.47 Set 1 wake-up
deviation), and resets if the
Tracking
(page 53).
status, bit 0).
status, bit 1).
status, bit 2).
status, bit 3).
status, bit 4).
status, bit 5).
(see page 273).
(see page 273).
(see page 273).
(see page 266).
(see page 266).
(see page 266).
(see page 189).
Def/FbEq16
0.0
1 = 1
0.0
1 = 1
0.00
(40.48
1 = 1
0.50
1 = 1
Not selected
40.50 Set
0
1
2
3
4
5
6
7
18
19
20
21
22
23
on page 162). -
Not selected
0
1

Hide quick links: