ABB ACS560 Firmware Manual page 307

General purpose drives
Table of Contents

Advertisement

No.
Name/Value
Ext PID max lim
Other [bit]
40.60
Set 1 PID activation
source
Off
On
Follow Ext1/Ext2
selection
DI1
DI2
DI3
DI4
DI5
DI6
Other [bit]
40.61
Setpoint scaling
actual
-200000.00...
200000.00 PID
customer units
40.62
PID internal
setpoint actual
-200000.00...
200000.00 %
40.65
Trim auto
connection
Disable
Enable
40.79
Set 1 units
User text
%
bar
kPa
Pa
psi
CFM
inH
O
2
Description
The process PID integration term is not decreased when the
output of the external PID has reached its maximum limit. In
this setup, the external PID is used as a source for the
process PID. This parameter is valid for the PID set 1.
Source selection (see
Terms and abbreviations
Selects the source of process PID set 1 activation.
Set 1 PID activation source is Off.
Set 1 PID activation source is On.
Selection follows the value of parameter
selection.
By changing to Ext2 control location, Process PID set 1 is
activated.
Digital input DI1
(10.02 DI delayed
Digital input DI2
(10.02 DI delayed
Digital input DI3
(10.02 DI delayed
Digital input DI4
(10.02 DI delayed
Digital input DI5
(10.02 DI delayed
Digital input DI6
(10.02 DI delayed
Source selection (see
Terms and abbreviations
Actual setpoint scaling. See parameter
scaling.
Scaling.
Displays the value of the internal setpoint. See the control
chain diagram on page 498.
This parameter is read-only.
Process PID internal setpoint.
Enable the PID trim auto connection and connects the
Process PID trim output act
frequency chains based on the trim selection parameter
40.52 Set 1 trim selection
Trim auto connection disabled.
Trim auto connection enabled.
Selects the unit for process PID setpoint, feedback and
deviation.
User text
%
bar
kPa
Pa
psi
CFM
inH
O
2
on page 162). -
19.11 Ext1/Ext2
status, bit 0).
status, bit 1).
status, bit 2).
status, bit 3).
status, bit 4).
status, bit 5).
on page 162). -
40.14 Set 1 setpoint
to either speed, torque or
or
41.52 Set 2 trim
selection.
Parameters 307
Def/FbEq16
3
On
0
1
2
3
4
5
6
7
8
0.00
1 = 1 PID
customer unit
-
1 = 1
40.05
Disable
0
1
°C
0
1
2
3
4
5
6
7