ABB ACS560 Firmware Manual page 297

General purpose drives
Hide thumbs Also See for ACS560:
Table of Contents

Advertisement

No.
Name/Value
In1+In2
In1-In2
In1*In2
In1/In2
MIN(In1,In2)
MAX(In1,In2)
AVE(In1,In2)
sqrt(In1)
sqrt(In1-In2)
sqrt(In1+In2)
sqrt(In1)+sqrt(In2)
40.11
Set 1 feedback filter
time
0.000...30.000 s
40.14
Set 1 setpoint
scaling
-200000.00...
200000.00
40.15
Set 1 output scaling
-200000.00...
200000.00
40.16
Set 1 setpoint 1
source
Not selected
Internal setpoint
AI1 scaled
AI2 scaled
Motor
potentiometer
Freq in scaled
AI1 percent
AI2 percent
Description
Sum of sources 1 and 2.
Source 2 subtracted from source 1.
Source 1 multiplied by source 2.
Source 1 divided by source 2.
Smaller of the two sources.
Greater of the two sources.
Average of the two sources.
Square root of source 1.
Square root of (source 1 - source 2).
Square root of (source 1 + source 2).
Square root of source 1 + square root of source 2.
Defines the filter time constant for process feedback.
Feedback filter time.
Defines, together with parameter
scaling, a general scaling factor for the external PID
control chain. The scaling can be utilized when, for
example, the process setpoint is input in Hz, and the
output of the PID controller is used as an rpm value in
speed control. In this case, this parameter might be set to
50, and parameter
40.15
Hz.
In effect, the output of the PID controller [40.15] when
deviation (setpoint - feedback) = [40.14] and [40.32] = 1.
Note: The scaling is based on the ratio between
and 40.15. For example, the values 50 and 1500 would
produce the same scaling as 1 and 3.
Process setpoint base.
See parameter
40.14 Set 1 setpoint scaling
Process PID controller output base.
Selects the primary source of process PID setpoint. See the
control chain diagram on page 495.
None.
Internal setpoint. See parameter
sel1.
12.12 AI1 scaled value
(see page 189).
12.22 AI2 scaled value
(see page 191).
22.80 Motor potentiometer ref act
potentiometer).
11.39 Freq in 1 scaled value
12.101 AI1 percent value
12.102 AI2 percent value
40.15
Set 1 output
to the nominal motor speed at 50
40.14
40.19 Set 1 internal setpoint
(output of the motor
(see page 187).
(see page 192)
(see page 192)
Parameters 297
Def/FbEq16
1
2
3
4
5
6
7
8
9
10
11
0.000 s
1 = 1 s
0.00
1=1
0.00
1=1
AI1 percent
0
2
3
4
8
10
11
12