ABB ACS560 Firmware Manual page 360

General purpose drives
Table of Contents

Advertisement

360 Parameters
No.
Name/Value
96.78
550 compatibility
mode
Disable
Enable
96.100 Change user pass
code
10000000...
99999999
96.101 Confirm user pass
code
10000000...
99999999
96.102 User lock
functionality
Bit
Name
0
Disable ABB access
levels
1
Freeze parameter
lock state
2
Disable file
download
3...6
Reserved
7
Disable panel
Bluetooth
8...10
Reserved
11
Disable OEM access
level 1
12
Disable OEM access
level 2
13
Disable OEM access
level 3
14...15 Reserved
Description
Enables/disables a Modbus user to access a select set of
parameters using 550 register numbering.
Using 550 compatibility mode is disabled.
Using 550 compatibility mode is enabled.
(Visible when user lock is open)
To change the current user pass code, enter a new code into
this parameter as well as
warning will be active until the new pass code is confirmed.
To cancel changing the pass code, close the user lock without
confirming. To close the lock, enter an invalid pass code in
parameter
96.02 Pass
code, activate parameter
Control board
boot, or cycle the power.
See also section
User lock
New user pass code.
(Visible when user lock is open)
Confirms the new user pass code entered in
user pass
code.
Confirmation of new user pass code.
(Visible when user lock is open)
Selects the actions or functionalities to be prevented by the
user lock. Note that the changes made take effect only when
the user lock is closed. See parameter
Note: We recommend you select all the actions and
functionalities unless otherwise required by the application.
Information
1 = ABB access levels (service, advanced programmer, etc.; see
96.03) disabled
1 = Changing the parameter lock state prevented, ie. pass code
358 has no effect
1 = Loading of files to drive prevented. This applies to
• firmware upgrades
• parameter restore
• changing home view of control panel
• editing drive texts
• editing the favorite parameters list on control panel
• configuration settings made through control panel such as
time/date formats and enabling/disabling clock display.
1 = Bluetooth disabled on ACS-AP-W control panel. If the drive is
part of a panel bus, Bluetooth is disabled on all panels.
1 = OEM access level 1 disabled
1 = OEM access level 2 disabled
1 = OEM access level 3 disabled
96.101 Confirm user pass
96.08
(page 96).
96.100 Change
96.02 Pass
Def/FbEq16
Enable
0
1
10000000
code. A
-
-
0000h
code.

Hide quick links:

Advertisement

Table of Contents
loading