Default control connections for the ABB standard (Vector) macro
1...10 kohm
Max.
500 ohm
7)
R3...R8
6)
X1
Reference voltage and analog inputs
1
2
3
AGND
4
5
6
AGND
7
8
9
AGND
X2, X3
Aux. voltage output and programmable digital inputs
10
11
DGND
5)
12
DCOM
13
14
15
16
17
18
X6, X7, X8 Relay outputs
19
RO1C
20
RO1A
21
RO1B
22
RO2C
23
RO2A
24
RO2B
25
RO3C
26
RO3A
27
RO3B
X5
Built-in fieldbus
29
30
31
DGND
(Frame R0...R2)
S100
TERM&BIAS
(Frame R3...R8)
S100
TERM
S200
Safety torque off
X4
R0...R2 R3...R8
33
-
34
SGND
35
OUT1
6)
36
IN1
10)
37
N2
X10
24 V AC/DC (frames R6...R8 only)
40
24 V AC/DC- in
41
24 V AC/DC+ in
X11
Redundant auxiliary voltage output
42
+24 V
43
DGND
44
DCOM
SCR
Signal cable shield (screen)
External speed reference: 0...10 V
AI1
see
22.11
Analog input circuit, common
+10V
10 V DC reference voltage
AI2
Not configured
Analog input circuit, common
Output frequency, 0...20 mA
AO1
see
13.12
Motor current, 0...20 mA
AO2
see
13.22
Analog output circuit common
+24V
Aux. voltage output +24 VDC, max. 250 mA
Aux. voltage output common
Digital input common for all
DI1
Stop (0) / Start (1): see
DI2
Forward (0) / reverse (1): see
DI3
Constant speed sel 1
DI4
Constant speed sel 2
DI5
Ramp 1 (0) / Ramp 2 (1)
DI6
Not configured
B+
Internal Modbus RTU (EIA-485), see
A-
control through the embedded fieldbus
interface (EFB)
Termination resistor and bias resistor switch
Termination resistor switch
BIAS
Bias resistor switch
OUT1
Safety torque off function. Factory connection.
OUT2
Both circuits must be closed for the drive to
SGND
start. See Safe torque off function in the drive
IN1
hardware manual.
IN2
24V AC/DC input, for control unit power supply
when external main power is disconnected.
Aux. voltage output +24 V DC, max. 250 mA
Aux. voltage output common
Digital input common for all
2)
9)
:
9)
:
20.03
20.03
4) 8)
: see
.22.22
4) 8)
: see
22.23
5) 8)
: see
9)
Ready Run
: see
10.24
250 V AC / 30 V DC
2 A
9)
Running
: see.
10.27
250 V AC / 30 V DC
2 A
9)
Fault(-1)
: see.
10.30
250 V AC / 30 V DC
2 A
1) 4) 8)
:
3)
23.11
Fieldbus
3)