366 Parameters
No.
Name/Value
Scalar
99.06
Motor nominal
current
0.0...32767.0
99.07
Motor nominal
voltage
0.0...32767.0 V
99.08
Motor nominal
frequency
0.00...500.00 Hz
99.09
Motor nominal
speed
0...30000 rpm
Description
Scalar control. Suitable for most applications, if top
performance is not required.
Motor identification run is not required.
Note: Scalar control must be used in the following situations:
• with multimotor systems 1) if the load is not equally shared
between the motors, 2) if the motors are of different sizes,
or 3) if the motors are going to be changed after the motor
identification (ID run)
• if the nominal current of the motor is less than 1/6 of the
nominal output current of the drive
• if the drive is used with no motor connected (for example,
for test purposes).
Note: Correct motor operation requires that the magnetizing
current of the motor does not exceed 90% of the nominal
current of the inverter.
See also section
Speed compensated stop
section
Operating modes of the drive
Defines the nominal motor current. Must be equal to the value
on the motor rating plate. If multiple motors are connected to
the drive, enter the total current of the motors.
Notes:
• Correct motor operation requires that the magnetizing
current of the motor does not exceed 90% of the nominal
current of the drive.
• This parameter cannot be changed while the drive is
running.
Nominal current of the motor. The allowable range:
• vector control mode: 1/6...2 × I
• scalar control mode: 0...2 × I
Note: When using flying start in scalar control mode (see
parameter
21.19 Scalar start
be in the range allowed for vector control mode.
Defines the nominal motor voltage supplied to the motor. This
setting must match the value on the rating plate of the motor.
Notes:
• The stress on the motor insulation is always dependent on
the drive supply voltage. This also applies to the case
where the motor voltage rating is lower than that of the
drive and the supply.
• This parameter cannot be changed while the drive is
running.
Nominal voltage of the motor.
Defines the nominal motor frequency. This setting must
match the value on the rating plate of the motor.
Note: This parameter cannot be changed while the drive is
running.
Nominal frequency of the motor.
Defines the nominal motor speed. The setting must match the
value on the rating plate of the motor.
Note: This parameter cannot be changed while the drive is
running.
Nominal speed of the motor.
(page 76), and
(page 37).
of the drive
N
with scalar control mode.
N
mode), the nominal current must
Def/FbEq16
1
1.8 A
1 = 0.01 A
See
46.05
400.0 V
10 = 1 V
50.00 Hz
10 = 1 Hz
1430 rpm
1 = 1 rpm