ABB ACS560 Firmware Manual page 210

General purpose drives
Table of Contents

Advertisement

210 Parameters
No.
Name/Value
Const time
Automatic
21.02
Magnetization time
0...10000 ms
21.03
Stop mode
Coast
Ramp
Description
The drive pre-magnetizes the motor before start. The pre-
magnetizing time is defined by parameter
Magnetization
time. This mode should be selected if constant
pre-magnetizing time is required (e.g. if the motor start must
be synchronized with the release of a mechanical brake).
This setting also guarantees the highest possible break-away
torque when the pre-magnetizing time is set long enough.
WARNING! The drive will start after the set
magnetizing time has passed even if motor
magnetization is not completed. In applications where
a full break-away torque is essential, ensure that the constant
magnetizing time is long enough to allow generation of full
magnetization and torque.
Automatic start guarantees optimal motor start in most cases.
It includes the flying start function (starting into a rotating
motor) and the automatic restart function. The drive motor
control program identifies the flux as well as the mechanical
state of the motor and starts the motor instantly under all
conditions.
Note: If parameter
99.04 Motor control mode
no flying start or automatic restart is possible unless
parameter
21.19 Scalar start mode
Defines the pre-magnetization time when
• parameter
21.01 Start mode
motor control mode), or
• parameter
21.19 Scalar start mode
scalar motor control mode).
After the start command, the drive automatically
premagnetizes the motor for the set time. To ensure full
magnetizing, set this parameter to the same value as, or
higher than, the rotor time constant. If not known, use the
rule-of-thumb value given in the table below:
Motor rated power
< 1 kW
1 to 10 kW
10 to 200 kW
200 to 1000 kW
Note: This parameter cannot be changed while the drive is
running.
Constant DC magnetizing time.
Selects the way the motor is stopped when a stop command
is received.
Additional braking is possible by selecting flux braking (see
parameter
97.05 Flux
braking).
Stops by switching off the output semiconductors of the drive.
The motor coasts to a stop.
WARNING! If a mechanical brake is used, ensure it is
safe to stop the drive by coasting.
Stops along the active deceleration ramp. See parameter
group
23 Speed reference ramp
Frequency reference chain
21.02
is set to Scalar,
is set to Automatic.
is set to
Const time
is set to
Const time
Constant magnetizing time
> 50 to 100 ms
> 100 to 200 ms
> 200 to 1000 ms
> 1000 to 2000 ms
on page
226
or
28
on page 240.
Def/FbEq16
1
2
500
(in vector
(in
1 = 1
Coast
0
1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents