172 Parameters
No.
Name/Value
05.81
Output frequency at
fault
-500.00...500.00
Hz
05.82
DC voltage at fault
0.00...2000.00 V
05.83
Motor current at
fault
05.84
Motor torque at fault
-1600.0...1600.0%
05.85
Main status word at
fault
0x0000...0xffff
05.86
DI delayed status at
fault
0b0000...0b1111
05.87
Inverter
temperature at fault
-40...160°C
05.88
Reference used at
fault
Description
Displays the output frequency (01.06) at which fault occurred. -
Output frequency at fault.
Displays the DC link volt age (01.11) at which fault occurred.
DC voltage at fault.
Displays the motor current (01.07) at which fault occurred.
Displays the motor torque (01.10) at which fault occurred.
Motor torque at fault.
Displays the main status word (06.11) at which fault occurred.
For the bit list, see parameter
Bit
Name
0
Ready to switch ON
1
Ready run
2
Ready ref
3
Tripped
4
Not in use
5
Not in use
6
Not in use
7
Warning
8
Modulating
9
Remote
10
Net OK
11
User bit 0
12
User bit 1
13
User bit 2
14
Charging
15
User bit 3
Main status word at fault.
Displays the DI delayed status (10.02) at which fault
occurred. For the bit list, see parameter
status.
DI delayed status at fault.
Displays the inverter temperature (05.11) at which fault
occurred.
Inverter temperature at fault.
Displays the reference used (28.01/23.01) at which fault
occurred. The type of the reference depends on the selected
operation mode (19.01).
06.11 Main status
word.
10.02 DI delayed
Def/FbEq16
See par.
46.02
-
10 = 1 V
-
-
See par.
46.03
0x0000
1 = 1
0b0000
1 = 1
-
1 = 1°C
-