198 Parameters
No.
Name/Value
13.28
AO2 source max
-32768.0...32767.0
13.29
AO2 out at AO2 src
min
0.000 ... 22.000 mA Minimum AO2 output value.
13.30
AO2 out at AO2 src
max
0.000 ... 22.000 mA Maximum AO2 output value.
13.91
AO1 data storage
-327.68...327.67
13.92
AO2 data storage
-327.68...327.67
19

19 Operation mode

19.01
Actual operation
mode
Zero
Speed
Torque
Min
Max
Add
Reserved
Description
Defines the real maximum value of the signal (selected by
parameter
13.22 AO2
source) that corresponds to the
maximum required AO2 output value (defined by parameter
13.30 AO2 out at AO2 src
source
min. See parameter
AO automatic scaling.
Real signal value corresponding to maximum AO2 output
value.
Defines the minimum output value for analog output AO2.
See also drawing at parameter
Defines the maximum output value for analog output AO2.
See also drawing at parameter
Storage parameter for controlling analog output AO1 e.g.
through the embedded fieldbus interface.
In parameter
13.12 AO1
Then set this parameter as the target of the incoming value
data. With the embedded fieldbus interface, simply set the
target selection parameter of that particular data
(58.101...58.114) to
AO1 data
Storage parameter for AO1.
Storage parameter for controlling analog output AO2 e.g.
through the embedded fieldbus interface.
In parameter
13.22 AO2
Then set this parameter as the target of the incoming value
data. With the embedded fieldbus interface, simply set the
target selection parameter of that particular data
(58.101...58.114) to
AO2 data
Storage parameter for AO2.
Selection of local and external control location sources and
operating modes.
See also section
Operating modes of the drive
Displays the operating mode currently used.
See parameters 19.11...19.14.
This parameter is read-only.
None.
Speed control (in vector motor control mode).
Torque control (in vector motor control mode).
The torque selector is comparing the output of the speed
controller
(25.01 Torque reference speed
reference
(26.74 Torque ref ramp
two is used (in vector motor control mode).
The torque selector is comparing the output of the speed
controller
(25.01 Torque reference speed
reference
(26.74 Torque ref ramp
two is used (in vector motor control mode).
The speed controller output is added to the torque reference
(in vector motor control mode).
max). See parameter
13.27 AO2
13.17 AO1 source min
13.27 AO2 source
13.27 AO2 source
source, select
AO1 data
storage.
source, select
AO2 data
storage.
(page 37).
control) and torque
out) and the smaller of the
control) and torque
out) and the greater of the
Def/FbEq16
3.2
about the
1 = 1
4.000 mA
min.
1000 = 1 mA
20.000 mA
min.
1000 = 1 mA
0.00
storage.
100 = 1
0.00
storage.
100 = 1
Scalar (Hz)
1
2
3
4
5
6
7...9