320 Parameters
No.
Name/Value
46.02
Frequency scaling
0.10...1000.00 Hz
46.03
Torque scaling
0.1...1000.0%
46.04
Power scaling
0.10 ...30000.00
kW or hp
46.05
Current scaling
0...30000 A
46.06
Speed ref zero
scaling
0.00 ... 30000.00
rpm
46.07
Frequency ref zero
scaling
0.00 ... 1000.00 Hz
46.11
Filter time motor
speed
2...20000 ms
46.12
Filter time output
frequency
2...20000 ms
46.13
Filter time motor
torque
2...20000 ms
46.14
Filter time power
2...20000 ms
Description
Defines the maximum frequency value used to define the
acceleration ramp rate and the initial frequency value used to
define deceleration ramp rate (see parameter group
Frequency reference
chain). The frequency acceleration and
deceleration ramp times are therefore related to this value
(not to parameter
30.14 Maximum
Also defines the 16-bit scaling of frequency-related
parameters. The value of this parameter corresponds to
20000 in e.g. fieldbus communication.
Acceleration/deceleration terminal/initial frequency.
Defines the 16-bit scaling of torque parameters. The value of
this parameter (in percent of nominal motor torque)
corresponds to 10000 in e.g. fieldbus communication.
Torque corresponding to 10000 on fieldbus.
Defines the output power value that corresponds to 10000 in
e.g. fieldbus communication. The unit is selected by
parameter
96.16 Unit
selection.
Power corresponding to 10000 on fieldbus.
Defines the 16-bit scaling of current parameters. The value of
this parameter corresponds to 10000 in fieldbus
communication.
Defines a speed corresponding to a zero reference received
from fieldbus (either the embedded fieldbus interface, or
interface FBA A). For example, with a setting of 500, the
fieldbus reference range of 0...20000 would correspond to a
speed of 500...[46.01] rpm.
Note: This parameter is effective only with the ABB Drives
communication profile.
Speed corresponding to minimum fieldbus reference.
Defines a frequency corresponding to a zero reference
received from fieldbus (either the embedded fieldbus
interface, or interface FBA A or FBA B). For example, with a
setting of 30, the fieldbus reference range of 0...20000 would
correspond to a speed of 30...[46.02] Hz.
Note: This parameter is effective only with the ABB Drives
communication profile.
Speed corresponding to minimum fieldbus reference.
Defines a filter time for signals
01.02 Motor speed
estimated.
Motor speed signal filter time.
Defines a filter time for signal
Output frequency signal filter time.
Defines a filter time for signal
Motor torque signal filter time.
Defines a filter time for signal
Output power signal filter time.
28
frequency).
01.01 Motor speed used
01.06 Output
frequency.
01.10 Motor
torque.
01.14 Output
power.
Def/FbEq16
50.00 Hz
10 = 1 Hz
100.0%
10 = 1%
1000.00 kW
1 = 1 unit
10000 A
0.00 rpm
1 = 1 rpm
0.00 Hz
10 = 1 Hz
and
500 ms
1 = 1 ms
500 ms
1 = 1 ms
100 ms
1 = 1 ms
100 ms
1 = 1 ms