ABB ACS560 Firmware Manual page 337

General purpose drives
Hide thumbs Also See for ACS560:
Table of Contents

Advertisement

No.
Name/Value
58.27
EFB ref2 type
58.28
EFB act1 type
Speed or frequency Type and scaling is chosen automatically according to the
Transparent
General
Torque
Reserved
Speed
Frequency
58.29
EFB act2 type
58.31
EFB act1
transparent source
Not selected
Other
58.32
EFB act2
transparent source
Not selected
Other
58.33
Addressing mode
Mode 0
Mode 1
Description
Selects the type and scaling of reference 2 received through
the embedded fieldbus interface. For the parameter selection,
see58.26 EFB ref1
type.
The scaled reference is displayed by
Selects the type of actual value 1.
currently active operation mode as follows.
Operation mode
(see par. 19.01)
Speed control
Torque control
Frequency control
No scaling is applied.
Generic reference without a specific unit. Scaling: 1 = 100.
Scaling is defined by parameter
Scaling is defined by parameter
Scaling is defined by parameter
Selects the type of actual value 2.
For the selections, see parameter
Selects the source of actual value 1 when parameter
EFB act1 type is set to
Transparent.
None.
Source selection (see
Terms and abbreviations
Selects the source of actual value 2 when parameter
EFB act2 type is set to
Transparent.
None.
Source selection (see
Terms and abbreviations
Defines the mapping between parameters and holding
registers in the 400101...465535 Modbus register range.
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter
Communication control (Refresh
16-bit values (groups 1...99, indexes 1...99):
Register address = 400000 + 100 × parameter group +
parameter index. For example, parameter 22.80 would be
mapped to register 400000 + 2200 + 80 = 402280.
32-bit values (groups 1...99, indexes 1...99):
Register address = 420000 + 200 × parameter group +
2 × parameter index. For example, parameter 22.80 would be
mapped to register 420000 + 4400 + 160 = 424560.
16-bit values (groups 1...255, indexes 1...255):
Register address = 400000 + 256 × parameter group +
parameter index. For example, parameter 22.80 would be
mapped to register 400000 + 5632 + 80 = 405712.
Parameters 337
03.10 EFB reference
Actual 1 type
Speed
Speed
Frequency
46.03 Torque
scaling.
46.01 Speed
scaling.
46.02 Frequency
scaling.
58.28 EFB act1
type.
58.28
on page 162). -
58.29
on page 162). -
58.06
settings).
Def/FbEq16
Torque
2.
Speed or
frequency
0
1
2
3
3
4
5
Transparent
Not selected
0
Other
(par.
01.07 Motor
current)
0
Mode 0
0
1