ABB ACS560 Firmware Manual page 429

General purpose drives
Table of Contents

Advertisement

Fault / Aux. code
Code
code visible only on
(hex)
assistant control panel
and drive composer)
64A1
Internal file load
64A4
Rating ID fault
64A6
Adaptive program
64B1
Internal SSW fault
1 – Starting OS time tick failed
2 – Creating system tasks failed
3 – Initializing file system failed
4 – Checking file system failed
64B2
User set fault
64B3
Macro
parameterization error
64E1
Kernel overload
6581
Parameter system
6591
Backup/Restore
timeout
65A1
FBA A parameter
conflict
6681
EFB comm loss
Programmable fault:
Communication loss
action
(aux
Cause
800A The application contains an
unknown target (system)
library function.
File read error.
Rating ID load error.
Fault in adaptive program.
A fatal error in the power-up
phase of System Software
(SSW).
Loading of user parameter set
failed because
• requested set does not exist
• set is not compatible with
control program
• drive was switched off
during loading.
Macro parameterization failed,
eg. Parameter default
value that cannot be changed
has been attempted to write.
Operating system error.
Parameter load or save failed.
During backup creating or
restoring operation a panel or
PC-tool has failed to
communicate with the drive as
part of this operation.
The drive does not have a
functionality requested by
PLC, or requested functionality
has not been activated.
Communication break in
embedded fieldbus (EFB)
58.14
communication.
What to do
Update the system library or reinstall
Automation Builder.
See the drive-specific log generated by
Automation Builder.
Reboot the control unit (using parameter
96.08 Control board
power. If the problem persists, contact
your local ABB representative.
Contact ABB.
Check the fault code extension.
SSW runs in partial functionality mode.
5 – Initializing WoRm volumes failed
6 – Loading FPGA configuration failed
7 – Loading application program failed
Ensure that a valid user parameter set
exists. Reload if uncertain.
Reboot the control unit (using parameter
96.08 Control board
power. If the problem persists, contact
your local ABB representative
Try forcing a save using parameter
Parameter save
Check panel or PC-tool communication
and if it is still in backup or restore state.
Check PLC programming.
Check settings of parameter groups
Fieldbus adapter (FBA)
settings.
Check the status of the fieldbus master
(online/offline/error etc.).
Check cable connections to the
EIA-485/X5 terminals 29, 30 and 31 on
the control unit.
Fault tracing 429
boot) or by cycling
boot) or by cycling
96.07
manually. Retry.
50
and
51 FBA A

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents