ABB ACS560 Firmware Manual page 104

General purpose drives
Table of Contents

Advertisement

104 Control macros
Terminal sizes
• (frames R0...R8): 0.14...1.5 mm
• Tightening torques: 0.5...0.6 N·m (0.4 lbf·ft)
Notes
1)
Current [0(4)...20 mA, R
input as selected with parameter 12.15 AI1 unit selection.
2)
Current [0(4)...20 mA, R
input as selected with parameter 12.25 AI2 unit selection.
3)
Total load capacity of the auxiliary voltage output +24V (X2:10) =
6.0 W (250 mA / 24 V) - User can use this source for either of the I/O connections
(DI1... DI2- RO1 or DI3...DI6 - RO2
4)
The constant speed are set based on the combination of sources as follows:
Source defined by
parameter
28.22
0
1
0
5)
The speed reference ramp is set based on the combination of sources as follows:
DI5
parameter
28.71
0
1
6
Connected with jumpers at the factory.
7)
Applicable for R0...R2 frames only.
8)
Use shielded twisted-pair cables for digital signals.
9)
Ground the outer shield of the cable 360 degrees under the grounding clamp on
the grounding shelf for the control cables.
10)
Input signal
11)
Output signal
For information on cable connection and drive operation, see Control Connections in
the hardware manual (3AXD50000044998).
2
(all terminals)
< 500 ohm] or voltage [ 0(2)...10 V, R
in
= 100 ohm] or voltage [ 0(2)...10 V, R
in
RO3).
~
Source defined by
parameter
28.23
0
0
1
Ramp set
Acc/Dec time 1
Acc/Dec time 2
Constant speed active
Set speed through AI1
Constant frequency 1
Constant frequency 2
Parameters
Scalar control (default)
28.72 Freq acceleration time 1
28.73 Freq deceleration time 1
28.74 Freq acceleration time 2
28.75 Freq acceleration time 2
> 200 kohm]
in
> 200 kohm]
in