No.
Name/Value
19.2 kbps
38.4 kbps
57.6 kbps
76.8 kbps
115.2 kbps
58.05
Parity
8 NONE 1
8 NONE 2
8 EVEN 1
8 ODD 1
58.06
Communication
control
Enabled
Refresh settings
Silent mode
Description
19.2 kbit/s.
38.4 kbit/s.
57.6 kbit/s.
76.8 kbit/s.
115.2 kbit/s.
Selects the type of parity bit and number of stop bits.
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter
Communication control (Refresh
Eight data bits, no parity bit, one stop bit.
Eight data bits, no parity bit, two stop bits.
Eight data bits, even parity bit, one stop bit.
Eight data bits, odd parity bit, one stop bit.
Takes changed EFB settings in use, or activates silent mode.
Normal operation.
Refreshes settings (parameters 58.01...58.05, 58.14...58.17,
58.25, 58.28...58.34) and takes changed EFB configuration
settings in use. Reverts automatically to Enabled.
Activates silent mode (no messages are transmitted).
Silent mode can be terminated by activating the
settings
selection of this parameter.
Parameters 333
58.06
settings).
Refresh
Def/FbEq16
3
4
5
6
7
8 EVEN 1
0
1
2
3
Enabled
0
1
2

Hide quick links: